![WEG SSW06 Скачать руководство пользователя страница 111](http://html.mh-extra.com/html/weg/ssw06/ssw06_user-manual_950614111.webp)
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
111
Range
[Factory Setting]
Parameter
Unit
Description / Notes
The copy function is used to transfer the content of the parameters
from one Soft-Starter SSW-06 to another. The Soft-Starters must be
of the same type (voltage/current) and the same software version
must be installed.
P215
(1)
0 to 2
Copy Function
[ 0=Inactive ]
-
P215
Action
Explanation
0 Inactive
-
1
Copy
Transfers the current parameter contents from the
SSW
→
HMI Soft-Starter and from Users 1 or 2 to the non-volatile (HMI)
keypad memory (EEPROM). The current Soft-Starter
parameters are not changed.
2
Paste
Transfers the contents of the non-volatile (HMI) keypad
HMI
→
SSW memory (EEPROM) to the current Soft-Starter SSW-06
parameters and to user 1 or 2 memories.
Table 6.24
- Copy function
tively, the Auto-Reset function will be disabled. A fault is considered
consecutive if it happens again within 30 seconds after Auto-Reset.
Thus if an error occurs four times consecutively, it will be displayed
permanently (and the Soft-Starter will be disabled).
Procedures
:
1. Connect the keypad to the Soft-Starter SSW-06 from which the
parameters will be copied (Soft-Starter A).
2. Set P215=1 (copy) for transferring the parameter from the Soft-Star-
ter A to the HMI. Press the key . While copy function is being
executed, the display will show
COPY
. P215 resets automatically
to 0 (Inactive) after the transfer has been completed.
3. Disconnect the keypad from the Soft-Starter SSW-06.
4. Connect the same keypad to the Soft-Starter SSW-06 to which the
parameters should be transferred (Soft-Starter B).
5. Set P215=2 (paste) for transferring the content from the non-volatile
keypad memory (EEPROM containing the parameters of the
Soft-Starter A) to the Soft-Starter B. Press the key . While the
keypad is executing the paste function, the display shows
COPY
.
When P215 returns to 0, the parameter transfer has been concluded.
Now Soft-Starters A and B have the same parameter content.
Please remember:
If Soft-Starters A and B command different motors, please check
the motor parameters of Soft-Starter B.
For copying the parameter contents from Soft-Starter A to other