CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
120
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Defines the action to be adopted when some errors relating to the
Serial or Fieldbus Communication occur.
For more information refer to the Serial Communication Manual
and/or to the Fieldbus Communication Manual for the Soft-Starter
SSW-06.
NOTE!
When Serial Communication or Fieldbus Communication is
not used, this parameter must remain at 0 (not used).
Allows time programming for the fault detection during the serial
Modbus-RTU communication. So you can adopt an action when, for
instance, the communication with the master of the Modbus-RTU
network is lost.
For more information, refer to the Soft-Starter SSW-06 Serial
Communication Manual.
NOTE!
This parameter must remain at 0 (not used), when the serial
communication is not being used.
P314
(1)
0 to 999
Timeout Time for
[ 0=Not Used ]
Serial Communication
1s
Telegram Reception
This parameter allows selecting the number of the first parameter,
which content will be sent from the Soft-Starter SSW-06 to the Master
of the Fieldbus network.
For more details, refer to the Soft-Starter SSW-06 Fieldbus Commu-
nication Manual.
P315
(1)
0 to 999
Read Parameter
[ 0 ]
via Fieldbus 1
-
Defines the protocol standards of the serial Modbus-RTU commu
-
nication.
For more information, refer to Serial Communication Manual for the
Soft-Starter SSW-06.
P312
(1)(2)
1 to 9
Protocol Type and
[ 1=Modbus-RTU
Transfer Rate of
(9600bps, no
the Serial
parity) ]
Communication -
Table 6.36
- Serial Communication Protocol Type
P313
0 to 3
Serial and Fieldbus
[ 0=Inactive ]
Communication Error
-
Actions
(E28, E29 and E30)
Table 6.37
- Error action of the Serial and Fieldbus Communication
P312
Action
1
Modbus-RTU (9600bps, no parity)
2
Modbus-RTU (9600bps, odd parity)
3
Modbus-RTU (9600bps, even parity)
4
Modbus-RTU (19200bps, no parity)
5
Modbus-RTU (19200bps, odd parity)
6
Modbus-RTU (19200bps, even parity)
7
Modbus-RTU (38400bps, no parity)
8
Modbus-RTU (38400bps, odd parity)
9
Modbus-RTU (38400bps, even parity)
P313
Action
0
Inactive
1
Disable
2
General Disable
3
Changes to Local
4
Inactive
5
Fatal Fault