CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
95
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P057
Minimum Line Fre
-
quency with the Motor
Running
It stores the lowest line frequency value with the motor in operation.
If P204 is set to 4, P057 is reset to zero.
This value remains stored even when the Soft-Starter is turned OFF.
0 to 99
[ - ]
1Hz
P058
Maximum Number of
Starts per Hour
It stores the maximum number of starts per hour.
It has the capacity of storing one start every 112.5 s, totalizing a
maximum of 32 starts in one hour. If two or more starts occur during
this time period of 112.5 s, only one is recorded.
If P204 is set to 4, P058 is reset to zero.
This value remains stored even when the Soft-Starter is turned OFF.
0 to 32
[ - ]
1
P059
Total Number of Starts
It stores the total number of starts executed by the Soft-Starter.
In order to be considered a start, the motor must initiate the starting
after the initial test, i.e., the line and motor connections must be
correct.
This value remains stored even when the Soft-Starter is turned OFF.
0 to 65535
[ - ]
1
P060, P063, P066,
P069, P072 and P075
Current at the Fault
Trip
P061, P064, P067,
P070, P073 and P076
Voltage at the Fault
Trip
P062, P065, P068,
P071, P074 and P077
SSW Status at the
Fault Trip
P060, P063, P066, P069, P072 and P075 stores the motor current
value at the moment of the fault trip, according to the table 6.2.
P061, P064, P067, P070, P073 and P076 stores the motor voltage
value at the moment of the fault trip, according to the table 6.2.
P062, P065, P068, P071, P074 and P077 stores the Soft-Starter
status at the moment of the fault trip, according to the table 6.2.
The Soft-Starter status are described in the parameter P006.
This value remains stored even when the Soft-Starter is turned
OFF.
0 to 9999.9
[ - ]
0.1A
0 to 999
[ - ]
0.1A
0 to 12
[ - ]
1
Table 6.2
-
Sequence of faults and their respective diagnostics
Sequence
of Faults
Related
Parameters
Parameter Descriptions
P014
(Last)
P060
Motor current at the last fault trip
P061
Line voltage at the last fault trip
P062
Soft-Starter status at the last fault trip
P015
(2nd)
P063
Motor current at the second fault trip
P064
Line voltage at the second fault trip
P065
Soft-Starter status at the second fault trip
P016
(3rd)
P066
Motor current at the third fault trip
P067
Line voltage at the third fault trip
P068
Soft-Starter status at the third fault trip
P017
(4th)
P069
Motor current at the fourth fault trip
P070
Line voltage at the fourth fault trip
P071
Soft-Starter status at the fourth fault trip
P018
(5th)
P072
Motor current at the fifth fault trip
P073
Line voltage at the fifth fault trip
P074
Soft-Starter status at the fifth fault trip
P019
(6t
h)
P075
Motor current at the sixth fault trip
P076
Line voltage at the sixth fault trip
P077
Soft-Starter status at the sixth fault trip