SSW-06 - QUICK PARAMETER REFERENCE
16
Parameter
Description
Adjustable Range
Factory
Unit
User´s
Page
Setting Setting
P296
(1)(2)
SSW Nominal Voltage
0=220/575
According to
V
116
1=575/690
Soft-Starter Nominal
Voltage
SERIAL COMMUNICATION PARAMETERS P300 to P399
P308
(1)(2)
Soft-Starter Address on the Serial
1 to 247
1
-
116
Communication Network
P309
(1)(2)
Fieldbus Communication
0=Inactive
0=Inactive
-
116
Board Enabling
1=Profibus-DP
(1 Input and 1 Output)
2=Profibus-DP
(4 Inputs and 4 Outputs)
3=Profibus-DP
(7 Inputs and 7 Outputs)
4=DeviceNet
(1 Input and 1 Output)
5=DeviceNet
(4 Inputs and 4 Outputs)
6=DeviceNet
(7 Inputs and 7 Outputs)
7= EtherNet/IP
(1 Input and 1 Output)
8= EtherNet/IP
(4 Input and 4 Output)
9= EtherNet/IP
(7 Input and 7 Output)
P310
Profibus Master Stop Detection
0=Inactive
0=Inactive
-
116
1=Active
P312
(1)(2)
Protocol Type and Serial
1=Modbus-RTU
1=Modbus-RTU
-
117
Communication Transfer Rate
(9600bps, no parity)
(9600bps,
2=Modbus-RTU
no parity)
(9600bps, odd)
3=Modbus-RTU
(9600bps, even)
4=Modbus-RTU
(19200bps, no parity)
5=Modbus-RTU
(19200bps, odd)
6=Modbus-RTU
(19200bps, even)
7=Modbus-RTU
(38400bps, no parity)
8=Modbus-RTU
(38400bps, odd)
9=Modbus-RTU
(38400bps, even)
P313
Serial and Fieldbus Communication
0=Inactive
0=Inactive
-
117
Error Actions (E28, E29 and E30)
1=Disable
2=General Disable
3=Changes to Local
4=Inactive
5=Fatal Fault
P314
(1)
Timeout Time for Serial
0 to 999
0=Not Used
s
117
Communication Telegram Reception
P315
(1)
Read Parameter via Fieldbus 1
0 to 999
0
-
117
P316
(1)
Read Parameter via Fieldbus 2
0 to 999
0
-
118
P317
(1)
Read Parameter via Fieldbus 3
0 to 999
0
-
118