CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
112
Range
[Factory Setting]
Parameter
Unit
Description / Notes
The Keypad can not be operated while it is executing the read or
write procedures.
NOTES!
1) If the Keypad (HMI) has saved parameters of a “different
version” than that installed in Soft-Starter SSW-06 to which it
is trying to copy the parameters, the operation will not be exe-
cuted and Soft-Starter SSW-06 will display error E10 (Error:
Copy Function not permitted). “Different Version” are those
that are different in “x” or “y”, supposing that the numbering
of Software Versions is described as
Vx.yz
.
2) This function changes all SSW-06 parameters to the new
values.
It allows the adjustment of the LCD Display contrast, as a function
of the viewing angle. Increase/decrease the parameter content until
the best contrast is obtained.
P218
0 to 150
LCD Display
[ 127 ]
Contrast Adjustment
-
Defines the command source that will select between the LOCAL /
REMOTE operation.
P220
(1)
0 to 10
LOCAL/REMOTE
[ 2 ]
Source Selection
-
Soft-Starter
A
Parameters
Soft-Starter
B
Parameters
SSW
→
HMI (copy)
HMI
→
SSW(copy)
Figure 6.12
- Parameter Copying from “Soft-Starter A” to “Soft-Starter B”
EEPROM
EEPROM
HMI
HMI
P215=1
Press.
P215=2
Press.
P220
Local/Remote Selection
Default Condition
0
Always Local Condition
Local
1
Always Remote Condition
Remote
2
Key of the Keypad
Local
3
Key of the Keypad
Remote
4
Digital Inputs DI4 ... DI6
(P266 ... P268)
5
Serial Communication
Local
6
Serial Communication
Remote
7
Fieldbus Communication
Local
8
Fieldbus Communication
Remote
9
SoftPLC
Local
10
SoftPLC
Remote
Table 6.25
- LOCAL/REMOTE Selection