CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
121
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Set this parameter value according to the motor nameplate and the
connection diagram in the terminal box.
The motor protection is based on the content of this parameter.
P400
(1)
0 to 999
Nominal Motor
[ 380 ]
Voltage 1V
Set this parameter value according to the motor nameplate.
The motor protection against current and the current limit are based
on this parameter content.
NOTES!
1) To ensure that these protections operate correctly, the nomi-
nal motor current must not be lower than 30% of the nominal
current of the Soft-Starter SSW-06.
2) The use of motors that operate with load duties lower than
50% of their rated loads are not recommended.
3) Program the nominal current of the motor according to the
power supply voltage.
P401
(1)
0 to 2424
Nominal Motor
[ 20 ]
Current 0.1A
This parameter allows selecting the number of the third parameter,
which content will be sent from the Soft-Starter SSW-06 to the Master
of the Fieldbus network.
For more details, refer to the Soft-Starter SSW-06 Fieldbus Commu-
nication Manual.
P317
(1)
0 to 999
Read Parameter
[ 0 ]
via Fieldbus 3
-
This parameter allows selecting the number of the second parame-
ter, which content will be sent from the Soft-Starter SSW-06 to the
Master of the Fieldbus network.
For more details, refer to the Soft-Starter SSW-06 Fieldbus Commu-
nication Manual.
P316
(1)
0 to 999
Read Parameter
[ 0 ]
via Fieldbus 2
-
6.5 MOTOR PARAMETERS - P400 to P499
Set the motor speed according to the motor nameplate data.
The motor speed must be the same as indicated on the motor na-
meplate, already considering its slip.
P402
(1)
Nominal Motor
Speed
400 to 3600
[ 1780 ]
1rpm
Set the motor power according to the motor nameplate data.
If the power is in CV or HP, multiply the value by 0.74kW.
P404
(1)
Nominal Motor
Power
0.1 to 2650
[ 75 ]
0.1kW
Set the Motor Power Factor according to the motor nameplate data.
P405
(1)
Motor Power
Factor
0 to 1.00
[ 0.89 ]
0.01