CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
122
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Table 6.38
- Braking methods selection
There are three braking methods implemented in the Soft-Starter
SSW-06. These braking methods should be used only when fast
stops are necessary.
Figure 6.18
- Braking torque
“Reverse Braking”
This is an efficient method to stop very high inertia loads.
The motor will stop via AC level voltage in reverse direction until
near 20% of the nominal speed when Optimal Braking is applied to
stop the motor.
The Reverse Braking AC level and Optimal Braking AC level are set
in P502.
Two contactors are needed.
It is compatible with the Soft-Starter SSW-06 inside delta motor
connection, except for two and eight pole motors.
P501
Stopped
Disable
Nominal
Speed
Braking
Torque
DC-Braking
Reverse Braking
Optimal Braking
P500
(1)
Braking Methods
0 to 3
[ 0=Inactive ]
-
Set the Service Factor according to the motor nameplate.
The current protections are based on the content of this parameter.
P406
(1)
0 to 1.50
Service Factor
[ 1.00 ]
0.01
6.6 SPECIAL FUNCTION PARAMETERS - P500 to P599
P500
Action
0
Inactive
1
Reverse Braking
2
Optimal Braking
3
DC-Braking