CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
137
Range
[Factory Setting]
Parameter
Unit
Description / Notes
The Overpower and Underpower values are adjusted in percentage
of the nominal motor power (P404).
P660 sets the immediate Underpower level at which the motor
can operate during the time adjusted in P661. After this time has
elapsed the Soft-Starter is disabled indicating Underpower fault.
This function can be used in applications with hydraulic pumps that
cannot operate without load.
P662 sets the immediate Overpower level at which the motor can
operate during the time adjusted in P663. After this time has elapsed
the Soft-Starter is disabled indicating Overpower fault.
For programming examples see the item 7.2.2.
NOTE!
These functions work only with full voltage, after the motor has
been started.
P660
(1)
Immediate
Underpower
P661
(1)
Immediate
Underpower Time
P662
(1)
Immediate Overpower
P663
(1)
Immediate Overpower
Time
0 to 99
[ 30 ]
1% Pn of the Motor
0 to 99
[ 0=Inactive ]
1s
0 to 99
[ 30 ]
1% Pn of the Motor
0 to 99
[ 0=Inactive ]
1s
Figure 6.32
- Trip levels for Overtorque and Undertorque
T(%)
0
P650
P652
Starting
Nominal
Stop
Run
Working Range
t(s)
T(%)
t
P650
P652
t(s)
Nominal
Fault Trip
Fault Trip
T(%)
Nominal
t(s)
t
P651
P653
Undertorque
Overtorque
P670
PT100 Inputs Card
Enable
0 to 1
[ 0=No ]
-
NOTE!
If it uses this motor temperature inputs board it cannot be used
the fieldbus communication board (kits KFB) or digital inputs
and outputs expansion board (K-IOE).
Table 6.47
- Motor temperature inputs board enable
This parameter enables motor temperature inputs board (optio-
nal kit K-PT100).
P670 Description
0
No
1
Yes