Vector Control
11
CFW700 | 11-13
P0406 – Motor Ventilation
Adjustable
Range:
0 = Self-Ventilated
1 = Separated Ventilation
2 = Optimal Flux
Factory
Setting:
0
Properties:
cfg
Access groups
via HMI:
MOTOR
Description:
During the Oriented Start-up Routine, the value adjusted in P0406 changes the parameters related to the motor
overload automatically, in the following manner:
Table 11.2:
Motor overload protection modification in function of P0406
P0406
P0156 (Overl.Curr.100 %)
P0157 (Overl.Curr.50 %)
P0158 (Overl.Curr.5 %)
0
1.05xP0401
0.9xP0401
0.65xP0401
1
1.05xP0401
1.05xP0401
1.05xP0401
2
1.05xP0401
1.0xP0401
1.0xP0401
ATTENTION!
Refer to the
section 11.4 - Optimal Flux for Sensorless Vector Control
, for more details on the use
of option P0406=2 (Optimal Flux).
P0407 – Motor Rated Power Factor
Refer to the
, for more details.
P0408 – Run Self-Tuning
P0409 – Motor Stator Resistance (Rs)
P0410 – Motor Magnetization Current (I
m
)
P0411 – Motor Flux Leakage Inductance (
σ
ls)
P0412 – Lr/Rr Constant (Rotor Time Constant – T
r
)
P0413 – T
m
Constant (Mechanical Time Constant)
Self-Tuning function parameters. Refer to item
Содержание CFW700
Страница 2: ......
Страница 4: ......
Страница 8: ...Summary...
Страница 34: ...2 General Information 2 4 CFW700...
Страница 38: ...3 About the CFW700 3 4 CFW700...
Страница 56: ...7 Starting up and Settings 7 4 CFW700...
Страница 58: ...8 Available Control Types 8 2 CFW700...
Страница 78: ...10 VVW Control 10 8 CFW700...
Страница 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...
Страница 184: ...16 Read only Parameters 16 12 CFW700...