P0298 - Application
Adjustable
Range:
0 = Normal Duty (ND)
1 = Heavy Duty (HD)
Factory
Setting:
0
Properties:
cfg
Access groups
via HMI:
Description:
Set the content of this parameter according to the application.
The
Normal Duty Regimen (ND)
defines the maximum current for continuous operation (I
nom-ND
) and an
overload of 110 % during 1 minute
. It must be used for driving motors that are not subject in that application
to high torques in relation to their rated torque, when operating in permanent regimen, during start, acceleration
or deceleration.
The
Heavy Duty Regimen (HD)
defines the maximum current for continuous operation (I
nom-HD
) and an
overload of 150 % during 1 minute.
It must be used for driving motors that are subject in that application
to high overload torques in relation to their rated torque, when operating in constant speed, during start,
acceleration or deceleration.
The I
nom-ND
and I
nom-HD
are presented in P0295. Refer to the CFW700 user's manual chapter 8 - Technical
Specifications, for more details regarding these operation regimens.
Содержание CFW700
Страница 2: ......
Страница 4: ......
Страница 8: ...Summary...
Страница 34: ...2 General Information 2 4 CFW700...
Страница 38: ...3 About the CFW700 3 4 CFW700...
Страница 56: ...7 Starting up and Settings 7 4 CFW700...
Страница 58: ...8 Available Control Types 8 2 CFW700...
Страница 78: ...10 VVW Control 10 8 CFW700...
Страница 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...
Страница 184: ...16 Read only Parameters 16 12 CFW700...