Vector Control
11
CFW700 | 11-17
11.8.2 Current Regulator
The parameters related to the CFW700 current regulator are presented in this group.
P0167 – Current Regulator Proportional Gain
Adjustable
Range:
0.00 to 1.99
Factory
Setting:
0.50
P0168 – Current Regulator Integral Gain
Adjustable
Range:
0.000 to 1.999
Factory
Setting:
0.010
Properties:
Vector
Access groups
via HMI:
Description:
Parameters P0167 and P0168 are adjusted automatically as a function of the parameters P0411 and P0409.
NOTE!
Do not change these parameters values.
11.8.3 Flux Regulator
The parameters related to the CFW700 flux regulator are presented next.
P0175 – Flux Regulator Proportional Gain
Adjustable
Range:
0.0 to 31.9
Factory
Setting:
2.0
P0176 – Flux Regulator Integral Gain
Adjustable
Range:
0.000 to 9.999
Factory
Setting:
0.020
Properties:
Vector
Access groups
via HMI:
Description:
These parameters are adjusted automatically in function of the parameter P0412. In general, the automatic
setting is sufficient and the readjustment is not necessary.
These gains must only be readjusted manually when the flux current signal (Id*) is unstable (oscillating) and
compromising the system operation.
NOTE!
For gains in P0175 > 12.0 the flux current (Id*) may become unstable.
Note:
(Id*) is observed at the analog outputs AO1 and/or AO2, by setting P0251=16 and/or P0254=16.
Содержание CFW700
Страница 2: ......
Страница 4: ......
Страница 8: ...Summary...
Страница 34: ...2 General Information 2 4 CFW700...
Страница 38: ...3 About the CFW700 3 4 CFW700...
Страница 56: ...7 Starting up and Settings 7 4 CFW700...
Страница 58: ...8 Available Control Types 8 2 CFW700...
Страница 78: ...10 VVW Control 10 8 CFW700...
Страница 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...
Страница 184: ...16 Read only Parameters 16 12 CFW700...