Digital and Analog Inputs and Outputs
13-22 | CFW700
P0293 – Tx Torque
Adjustable
Range:
0 to 200 %
Factory
Setting:
100 %
Properties:
Access groups
via HMI:
Description:
It is used in the
Torque > Tx
and
Torque < Tx
functions of the digital and relay outputs.
In those functions the motor torque indicated in P0009 is compared with the value adjusted in P0293.
The setting of this parameter is expressed as a percentage of the motor rated current (P0401=100 %).
P0294 – Hx Time
Adjustable
Range:
0 to 6553 h
Factory
Setting:
4320 h
Properties:
Access groups
via HMI:
Description:
It is used in the
Enabled Hours > Hx
function of the digital and relay outputs.
13.2 LOCAL AND REMOTE COMMAND
In those parameter groups one can configure the origin of the main inverter commands when in the LOCAL or in
the REMOTE situation, as the Speed Reference, Speed Direction, Run/Stop and JOG.
P0220 – LOCAL/REMOTE Selection Source
Adjustable
Range:
0 = Always Local
1 = Always Remote
2 = Local/Remote Key Local
3 = Local/Remote Key Remote
4 = DIx
5 = Serial Local
6 = Serial Remote
7 = CANopen / DeviceNet / Profibus DP Local
8 = CANopen / DeviceNet / Profibus DP Remote
9 = SoftPLC Local
10 = SoftPLC Remote
Factory
Setting:
2
Properties:
cfg
Access groups
via HMI:
I/O
Description:
It defines the origin of the command that will select between the LOCAL situation and the REMOTE situation,
where:
LOCAL: Means Local Default situation.
REMOTE: Means Remote Default situation.
DIx: Refer to
Содержание CFW700
Страница 2: ......
Страница 4: ......
Страница 8: ...Summary...
Страница 34: ...2 General Information 2 4 CFW700...
Страница 38: ...3 About the CFW700 3 4 CFW700...
Страница 56: ...7 Starting up and Settings 7 4 CFW700...
Страница 58: ...8 Available Control Types 8 2 CFW700...
Страница 78: ...10 VVW Control 10 8 CFW700...
Страница 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...
Страница 184: ...16 Read only Parameters 16 12 CFW700...