3
3-2 | CFW-11M RB
Installation and Connection
Table 3.1 -
Currents and configuration in 380 / 480 V
Nominal Current (A)
Number of Power Units UP11-02
ND
HD
600
515
1
1140
979
2
1710
1468
3
2280
1957
4
2850
2446
5
Table 3.2 -
Currents and configuration in 500 / 600 V
Nominal Current (A)
Number of Power Units UP11-01
ND
HD
470
380
1
893
722
2
1340
1083
3
1786
1444
4
2232
1805
5
Table 3.3 -
Currents and configuration in 660 / 690 V
Nominal Current (A)
Number of Power Units UP11-01
ND
HD
427
340
1
811
646
2
1217
969
3
1622
1292
4
2028
1615
5
Each cable set contains one optical fiber and one DB-25 cable. Both cables are for the connections between
the IPS1 board (control unit) and the CIM1 board (power unit).
Table 3.4 -
Cable sets
Weg Part
Number
Optical Fiber Length
mm (in)
DB-25 Cable Length
mm (in)
10411757
2350 (92.52)
2550 (100.39)
10509891
2800 (110.24)
3000 (118.11)
10411758
3400 (133.86)
3600 (141.73)
10411759
3900 (153.54)
4100 (161.42)
The cable sets that come with the control sets are described in the table 3.5.
Table 3.5 -
Number of cable sets
Number of Power Units
Number of Cable Sets
1
1X 10411757
2
2X 10411757
3
2X 10411757
1X 10509891
4
2X 10411757
1X 10509891
1X 10411758
5
2X 10411757
1X 10509891
1X 10411758
1X 10411759
The panel integrator is responsible for the other components of the panel, such as, the power bus bars, the
pre-charge circuit, the panel fans, the protection fuses, input filter, etc.