Locking time
The locking time enables the heat pump to reach
a stable operating state before the supplementary
source is allowed to switch on.
The supplementary source is released only when
the locking time has elapsed.
The locking time starts as soon as a valid flow
temperature setpoint is available.
Calculation of the release integral starts only when
the locking time has elapsed.
TVxSch Actual value of common flow temperature
TVwSch Setpoint of common flow temperature
A
Request
QX2 Release output QX2
T
Locking time
QX2
No consideration is given to the locking time, if
the heat pump malfunctions or is locked, or if the
supplementary source must end DHW charging.
Setting "- - -" can be used to deactivate the
function.
Содержание WO*A060LDC Series
Страница 4: ...1 OUTDOOR UNIT DTW_1SP003E_02 CHAPTER01 2013 2 28 SINGLE PHASE TYPE WO A060LDC WO A080LDC WO A100LDT...
Страница 13: ...OU01 08 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LD OUTDOOR UNIT WO A060 100LD MODELS WO A100L Unit mm...
Страница 17: ...OU01 12 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LD OUTDOOR UNIT WO A060 100LD MODELS WO A080L...
Страница 18: ...OU01 13 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LD OUTDOOR UNIT WO A060 100LD MODELS WO A100L...
Страница 32: ...2 HYDRAULIC UNIT DTW_1SP003E_02 CHAPTER02 2013 03 22 SINGLE PHASE TYPE WS A050DD6 WS A100DD6...
Страница 46: ...3 CONTROL SYSTEM DTW_1SP003E_02 CHAPTER03 2013 03 22 WS A050DD6 Hydraulic unit WS A100DD6 Hydraulic unit...
Страница 125: ...CS01 78 Control system CS01 78 CONTROL SYSTEM CONTROL SYSTEM...