Floor curing function
Off
•
The function is deactivated.
Heating operational (Fh)
•
The first part of the temperature profile is
automatically completed.
Heating "ready for occupancy" (Bh)
•
The second part of the temperature profile is
handled automatically.
Heating "ready for occupancy" /
•
Heating operational
The full temperature profile (1st and 2nd part) is
performed automatically.
Manual
•
No temperature profile is performed, but the control
is performed according to the "manual controlled
drying setpoint". The function is automatically
terminated after 25 days
Important:
The standards and directions of the building
-
contractor must be followed!
This function will not work properly unless
-
the installation has been adequately made
(hydraulics, electricity, settings). Otherwise, the
floors to be dried may be damaged!
The function may be prematurely interrupted by
-
setting it to Off.
The maximum flow temperature limitation
-
remains active.
Heat pump
flow temp
X : Starting day
Days
Bh
Fh
Fh + Bh
Floor curing setpoint manually
The flow temperature setpoint for the "Manually"
controlled floor drying function can be adjusted
respectively for each heating circuit.
Floor curing day current
Displays the current flow temperature setpoint for
the controlled floor drying function.
Floor curing day completed
Displays the current day of the controlled floor
drying function.
Important:
After a power outage, the installation resumes the
controlled drying function as it was when the
outage occurred.
Operating Mode Changeover
LINE
FUNCTION
HC1
HC2
900
1200
Operating mode changeover
(None / Protection / Reduced / Comfort / Automatic)
In case of an external changeover via input H2 (on
the extension module only) the operating mode to
which the changeover will be performed must be
previously defined.
Содержание WO*A060LDC Series
Страница 4: ...1 OUTDOOR UNIT DTW_1SP003E_02 CHAPTER01 2013 2 28 SINGLE PHASE TYPE WO A060LDC WO A080LDC WO A100LDT...
Страница 13: ...OU01 08 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LD OUTDOOR UNIT WO A060 100LD MODELS WO A100L Unit mm...
Страница 17: ...OU01 12 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LD OUTDOOR UNIT WO A060 100LD MODELS WO A080L...
Страница 18: ...OU01 13 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LD OUTDOOR UNIT WO A060 100LD MODELS WO A100L...
Страница 32: ...2 HYDRAULIC UNIT DTW_1SP003E_02 CHAPTER02 2013 03 22 SINGLE PHASE TYPE WS A050DD6 WS A100DD6...
Страница 46: ...3 CONTROL SYSTEM DTW_1SP003E_02 CHAPTER03 2013 03 22 WS A050DD6 Hydraulic unit WS A100DD6 Hydraulic unit...
Страница 125: ...CS01 78 Control system CS01 78 CONTROL SYSTEM CONTROL SYSTEM...