Basic unit EX/E
LINE
FUNCTION
5981
5983
5985
Contact type input EX1, EX2, EX3
The type of contact can be selected:
NC
The input’s function is active when voltage is not
present.
NO
The input’s function is active when voltage is
present.
The descriptions relating to the functions of the EX
contact apply when an NO contact is selected.
Sensor Corrections
LINE
FUNCTION
6098
Not used
6100
Readjustment outside sensor
The outdoor temperature measuring value can
-
be corrected within a range of +/- 3 K.
Installation Frost Protection
LINE
FUNCTION
6120
Frost protection for the plant
According to the outdoor temperature, the heating
circuit pump and the condenser pump are switched
on although there is no demand for heat.
Outdoor
temperature
Pump
ON
Periodically ON
OFF
Diagram
Continuously ON
Set to ON for 10 min, approx. every
6 hours.
Continuously OFF
ON
Periodically ON
OFF
-6
-5
-4
-3
-2
-1
0
1
2
3
4
TA °C
…-4°C
-5…1.5°C
1.5°C…
Miscellaneous
LINE
FUNCTION
6205
Reset to default parameters
6220
Software version
Содержание WO*A060LDC Series
Страница 4: ...1 OUTDOOR UNIT DTW_1SP003E_02 CHAPTER01 2013 2 28 SINGLE PHASE TYPE WO A060LDC WO A080LDC WO A100LDT...
Страница 13: ...OU01 08 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LD OUTDOOR UNIT WO A060 100LD MODELS WO A100L Unit mm...
Страница 17: ...OU01 12 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LD OUTDOOR UNIT WO A060 100LD MODELS WO A080L...
Страница 18: ...OU01 13 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LD OUTDOOR UNIT WO A060 100LD MODELS WO A100L...
Страница 32: ...2 HYDRAULIC UNIT DTW_1SP003E_02 CHAPTER02 2013 03 22 SINGLE PHASE TYPE WS A050DD6 WS A100DD6...
Страница 46: ...3 CONTROL SYSTEM DTW_1SP003E_02 CHAPTER03 2013 03 22 WS A050DD6 Hydraulic unit WS A100DD6 Hydraulic unit...
Страница 125: ...CS01 78 Control system CS01 78 CONTROL SYSTEM CONTROL SYSTEM...