Heating curve slope
Based on the heating characteristic, the controller
computes the flow temperature setpoint which will
be used for controlling the flow temperature in
consideration of atmospheric conditions. Different
settings can be used to adapt the heating
characteristic so that the heating capacity, and
therefore the room temperature, will match the
individual needs.
The colder the outdoor temperature, the greater the
extent to which the slope will modify the flow
temperature. In other words, the slope should be
corrected if the room temperature shows a
difference when the outdoor temperature is low, but
not when it is high.
Increase the setting:
-
The flow temperature is increased mainly when
the outdoor temperatures are low.
Decrease the setting:
-
The flow temperature is lowered mainly when the
outdoor temperatures are low.
Warning:
The heating curve is adjusted in relation to a room
temperature setpoint of 20°C. If the room
temperature setpoint is modified, the flow
temperature setpoint is automatically recomputed.
This will not modify the setting and amounts to
automatically adapting the curve.
20
30
40
50
60
70
-20,0
-15,0
-10,0
-5,0
0,0
5,0
10,0
15,0
20,0
Outdoor Temperature (°C)
0,25
0,5
0,75
1
1,25
1,5
1,75
2
Heating Curves
Heating curve displacement
The curve displacement (offset) modifies the flow
temperature in a general and even manner over the
full range of outdoor temperature. In other words,
the displacement should be corrected when the
room temperature is generally too high or too low.
Содержание WO*A060LDC Series
Страница 4: ...1 OUTDOOR UNIT DTW_1SP003E_02 CHAPTER01 2013 2 28 SINGLE PHASE TYPE WO A060LDC WO A080LDC WO A100LDT...
Страница 13: ...OU01 08 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LD OUTDOOR UNIT WO A060 100LD MODELS WO A100L Unit mm...
Страница 17: ...OU01 12 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LD OUTDOOR UNIT WO A060 100LD MODELS WO A080L...
Страница 18: ...OU01 13 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LD OUTDOOR UNIT WO A060 100LD MODELS WO A100L...
Страница 32: ...2 HYDRAULIC UNIT DTW_1SP003E_02 CHAPTER02 2013 03 22 SINGLE PHASE TYPE WS A050DD6 WS A100DD6...
Страница 46: ...3 CONTROL SYSTEM DTW_1SP003E_02 CHAPTER03 2013 03 22 WS A050DD6 Hydraulic unit WS A100DD6 Hydraulic unit...
Страница 125: ...CS01 78 Control system CS01 78 CONTROL SYSTEM CONTROL SYSTEM...