- (CS01 - 29) -
Control system
- (CS01 - 29) -
C
O
N
TR
O
L
SY
ST
EM
C
O
N
TR
O
L
SY
ST
EM
Heating Circuit Frost Protection
Informations:
The heating circuit frost protection is continuously
activated (protection mode ) and is not
adjustable.
Heating circuit frost protection in heating mode:
-
If the flow temperature is below 5°C, the controller
initiates the production of heat and starts the
heating pumps, regardless of the current heating
mode.
If the flow temperature rises again above 7°C,
the controller waits another 5 minutes, and then
stops the production of heat and the heating
pumps.
Heating circuit frost protection in cooling mode:
-
See Cooling mode.