Domestic hot water functions
z
The control sets the DHW temperature, according
to the time program or continuously, to the desired
setpoint. The priority of DHW charging over room
heating is adjustable in this case
The controller has a configurable legionella
function designed for protection against legionella
in the storage tank and the pipes. The circulation
pump is controlled according to the current time
program and operating mode.
Setpoint value
LINE
FUNCTION
1610
Nominal setpoint
1612
Reduced setpoint
The DHW is heated to various setpoint values.
These setpoints are active according to the selected
operating mode and allow the desired temperatures
to be reached in the DHW storage tank.
Reduced setpoint Nominal setpoint
DHW max setpoint
0
10
20
30
40
50
60
70 °C
Important:
For optimal operation we recommend reducing the
setpoints to the lowest value.
Setpoints which are too high may interfere with
heating and cause some discomfort. In this case
DHW/Heating changeover cycles may successively
occur
If DHW charge boosting is not desired during
the day, we recommend adjusting the reduced
temperature setpoint to 15°C. Full charging will
occur during the night at the nominal temperature..
Содержание WO*A060LDC Series
Страница 4: ...1 OUTDOOR UNIT DTW_1SP003E_02 CHAPTER01 2013 2 28 SINGLE PHASE TYPE WO A060LDC WO A080LDC WO A100LDT...
Страница 13: ...OU01 08 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LD OUTDOOR UNIT WO A060 100LD MODELS WO A100L Unit mm...
Страница 17: ...OU01 12 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LD OUTDOOR UNIT WO A060 100LD MODELS WO A080L...
Страница 18: ...OU01 13 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LD OUTDOOR UNIT WO A060 100LD MODELS WO A100L...
Страница 32: ...2 HYDRAULIC UNIT DTW_1SP003E_02 CHAPTER02 2013 03 22 SINGLE PHASE TYPE WS A050DD6 WS A100DD6...
Страница 46: ...3 CONTROL SYSTEM DTW_1SP003E_02 CHAPTER03 2013 03 22 WS A050DD6 Hydraulic unit WS A100DD6 Hydraulic unit...
Страница 125: ...CS01 78 Control system CS01 78 CONTROL SYSTEM CONTROL SYSTEM...