Purge your flue gas analyzer into fresh air, let it stabilize
and ensure you have:
O readings of 20.6 or above
CO
2
readings of below 0.2% CO .
Yes
(repeat the process for minimum)
Boiler is operating correctly and within
the combustion limits, bring the boiler
out of the Service Mode and no further
adjustments are required.
No
Boiler combustion limits are not met, if
all previous checks have been
completed correctly e.g. gas pressure,
gas rate, flue integrity and re-circulation
then please run FTF / please follow FTF
procedure. If FTF is not enough for
correct emission values, please run
Auto Calibration / please follow Auto
Calibration procedure.
Run the boiler in maximum/minimum
output e.g. Service Mode
Insert your flue gas analyzer in the appliance test point and ensure
the appliance is maintaining maximum/minimum power output and
allow the readings on the analyzer to stabilize.
Readings should be:
CO - less than 300 ppm
CO/CO
2
ratio -0.004 or below
Start
4.3. CO/CO2 Combustion Check
CAUTION