27
warmhaus.co.uk
External Connections
1 Boiler
2 Visible air break
3 38mm minimum trap
4 Visible air break and trap not required if there is a trap
with a minimum condensate seal of 38 mm incorporated
into the boiler – refer to manufacturer’s instructions
5 External length of pipe 3 m maximum
6 Open end of condensate discharge pipe direct into
gully 25 mm min below grating but above water level;
end cut at 45 °
7 Minimum internal diameter 19 mm
8 Pipe size transition point
9 Minimum internal diameter 30 mm
10 Water/weatherproof insulation
11 Fit drain cover/leaf guard
Internal Condensate Pipe Discharge Termination
1 Condensate discharge pipe from boiler
2 Ground (this section of the condensate discharge pipe
may be run either above or below round level); End cut
at 45°
3 Diameter 100 mm minimum plastic tube
4 Bottom of tube sealed
5 Limestone chippings
6 Two rows of three 12 mm holes at 25 mm centres, 50
mm from bottom of tube and facing away from house
7 Hole depth 400 mm minimum by 300 mm diameter
8 Minimum internal diameter 19 mm
9 Pipe size transition point
10 Minimum internal diameter 30 mm
11 Water/weatherproof insulation
0071_00.WUK200821
0072_00.WUK200821
Example of a purpose made soakaway