STEP 7
- Insert the 500mm long flue terminal onto the flue extension starter piece using the
supplied silicone grease lubricant if necessary.
STEP 8
- Secure the flue terminal with 3 x supplied flue terminal fixing screws. It is necessary to
drill 3mm pilot holes through the 100mm flue wall ONLY. DO NOT drill through the 80mm flue
wall. Use the short screws if NOT using the plastic weather proof collar on the terminal. Use the
long screws if using the plastic weatherproof collar. DO NOT use longer screws that would
puncture the 80mm flue wall!
NOTE – The flue terminal must ALWAYS be secured following the guidance in step 8. This
includes installations where the flue is extended with additional lengths of flue and fittings (refer
to Section 3.4.3). The plastic collar on the flue terminal is intended for use with pitched or flat
roof flashings.
X3
X3
7
8
8
Figure 74: Flue Terminal Installation
OR