8. System Maintenance
After the system is powered off, there is still residual power and heat in the enclosure,
which may cause electric shock or burns. Therefore, in the systemTo operate the
accumulator 5 minutes after the power is off, protective gloves should be worn. Only when
all lights of the accumulator are off
Only then can the energy storage be maintained.
System power-off operation steps:
Step 1 Turn off the circuit breaker switch on the inverter with the battery pack input.
Step 2 Turn off the power button switch on all battery packs to ensure that all LEDs are
successfully turned off and all LEDs are off.
Observe whether the appearance of energy storage is
damaged or deformed. Listen to whether there is any
abnormal sound during the operation of theenergy
storage.
When the accumulator is running, check whether the
energy storage battery indicator is correct.
First commissioning and
testing half a year after this
It is then done every six
months to a year.
Check for disconnected or loose cable connections.
Check the cable for any damage,especially if there are
cuts in the sheath where the cable is in contact with the
metal surface.
Check that unused DC input terminals,energy storage
terminals, COM ports,and cable covers are locked.
Check that the grounding cable is reliably grounded.
8.1 System Power off
8.2 Routine Maintenance
WY51100
Project
System
cleanliness
Regularly check the radiator for
covered or dirty
Once every six months.
Every six months
to once a year.
System
operating
status
Electrical
connection
Grounding
reliability
Method
Maintenance interval
77
Содержание WYIN36
Страница 1: ...5kW Hybrid Inverter 10kWh Energy Storage System User Manual...
Страница 3: ...HYBRID ON GRID SOLAR INVERTER USER MANUAL Model WYIN36 WYIN46 WYIN5K User Manual...
Страница 11: ...3 Product Description Figure 1 WYIN5K 09 3 1 Inverter Overview Model WYIN5K Overview see Figure 1...
Страница 33: ...3 Enable the parallel function WYIN5K 31...
Страница 37: ...3 Enable the group three phase function WYIN5K 35...
Страница 43: ...1 Battery parameter settings This submenu interface contains 11 options divided into 3 pages WYIN5K 41...