3.7.2 EPS (Emergency Power Supply) Connection
The EPS can provide a maximum output power of 4500w, and an emergency load can be
connected to the EPS port. It is crucial to install an AC isolator or other load disconnection device
between the EPS output of the inverter and the emergency load to ensure safe operation in case of
an emergency. We recommend using an AC leakage circuit breaker with a specification of at least
32A to ensure proper protection.
The cable length should not exceed 50 meters, because the line resistance existing on the
cable will cause a large power loss.
Be sure to install a separate AC circuit breaker or other load disconnect device between the
inverter and the grid to ensure that the inverter can safely disconnect the load in an
emergency.
The maximum output power of EPS is 4500w for the GH5000TL and GH4600TL models, and
3600W for the GH3600TL model. If the load is continuously greater than 4500W or 3600W,
the inverter will stop outputting. Please note that the output power of EPS depends on the
battery capacity.
Note: Do not connect to the grid, in case the machine is damaged due to wrong wiring!
WYIN5K
21
Содержание WYIN36
Страница 1: ...5kW Hybrid Inverter 10kWh Energy Storage System User Manual...
Страница 3: ...HYBRID ON GRID SOLAR INVERTER USER MANUAL Model WYIN36 WYIN46 WYIN5K User Manual...
Страница 11: ...3 Product Description Figure 1 WYIN5K 09 3 1 Inverter Overview Model WYIN5K Overview see Figure 1...
Страница 33: ...3 Enable the parallel function WYIN5K 31...
Страница 37: ...3 Enable the group three phase function WYIN5K 35...
Страница 43: ...1 Battery parameter settings This submenu interface contains 11 options divided into 3 pages WYIN5K 41...
Страница 57: ...HOME ENERGY STORAGE SYSTEM Model WY51100 User Manual...