background image

13

Fig.12a

EXTENDING THE FLUE

Connect the bend – supplied with the terminal kit – to the top 

of the boiler using clamp (supplied) see fig. 11. The additional 

bends & extensions have push-fit connections, care should be 

taken to ensure that the correct seal is made when assembling 

the flue system. Connect the required number of flue exten

-

sions or bends (up to the maximum equivalent flue length) to 

the flue terminal  (see fig. 11-14).

 

The flue system should have 

a minimum of 1º; maximum of 3º rise from the boiler to outside, 

to ensure any condense fluid that forms, is allowed to drain 

back to the appliance.

NOTE

When cutting an extension to the required length, you must 

ensure that the excess is cut from the plain end of the extension 

(see fig. 11-14). Remove any burrs, and check that all seals are 

located properly. You must ensure that the entire flue system is 

properly supported and connected. Seal the flue assembly to 

the wall using cement or a suitable alternative that will provide 

satisfactory weatherproofing. The interior and exterior trim can 

now be fitted.

4.5.2 CONCENTRIC VERTICAL FLUE

The appliance can be used with either the Vokèra condensing 

60/100mm concentric flue system or the optional 80/125mm 

concentric flue system.  

NOTE

These instructions relate 

only

 to the Vokèra condensing 

60/100mm concentric flue system. For specific details on the 

installation of the 80/125mm concentric flue system please refer 

to the instructions supplied.

The vertical flue terminal can be connected directly to the ap

-

pliance flue outlet. Alternatively, an extension or bend can be 

connected to the appliance flue outlet if desired, however if 

additional bends are fitted, a reduction must be made to the 

maximum flue length (see table below).

Reduction for bends

 

Bend  

Reduction in maximum flue length for each bend

 45º bend  1.0 metre (60/100) - 1.0 metre (80/125) 
 90º bend  1.0 metre (60/100) - 1.5 metre (80/125) 

Vertical flue terminal and accessories

  

Part No. 

Description  

Length

 

  29450122  Vertical flue terminal  

1000mm 

  531 

Pitched roof flashing plate 

N/A 

  532 

Flat roof flashing plate 

N/A 

  29450123  90-degree bend 

N/A 

  29450124  45-degree bends (pair) 

N/A 

  29450125  500mm extension 

500mm 

  29450126  1000mm extension 

1000mm 

  29450127  2000mm extension 

2000mm 

  29450128  Telescopic extension 

372/519mm

  529 

Wall bracket pack (5) 

208mm

Using the dimensions given in fig. 12 as a reference, mark and 

cut a 125mm hole in the ceiling and/or roof.

Fig. 12b

Fig. 12c

Fit the appropriate flashing plate to the roof and insert the ver

-

tical flue terminal through the flashing plate from the outside, 

ensuring that the collar on the flue terminal fits over the flashing.

The fixing holes for the wall-mounting bracket should now be 

drilled and plugged, an ‘appropriate type and quantity of fixing 

should be used to ensure that the bracket is mounted securely. 

Once the bracket has been secured to the wall, mount the ap-

pliance onto the bracket.

A

Fig. 12

Содержание Excel 25

Страница 1: ...S TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK Excel High ef...

Страница 2: ...3A 5 Air supply 11 3A 6 Water circulation 11 3A 7 Electrical supply 11 3A 8 Mounting on a combustible surface 11 3A 9 Timber framed buildings 11 3A 10 Inhibitors 11 3A 11 Showers 11 3A 12 Declaration...

Страница 3: ...el boiler has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and efficiency Please therefore take some ti...

Страница 4: ...et temperature or counter clockwise to reduce the temperature range 37 C 60 C Boiler at OFF standby Select this position when you want the boiler to be switched off for short periods days or if the bo...

Страница 5: ...may be necessary to reduce the flow of water at the hot water outlet tap NOTE If the appliance fails to ignite during the ignition sequence it will enter a lockout condition Should this occur please a...

Страница 6: ...switch in the bottom position To select OFF mode move the selector switch in the upper position APPLIANCE STATUS LED AND FAULT CODES Fig 3 4 WHAT IF 5 SETTING THE VOK RA Advice for homeowners Please c...

Страница 7: ...use with a sealed system only consequently they are not intended for use on open vented systems This booklet is an integral part of the appliance It is therefore necessary to ensure that the booklet...

Страница 8: ...the boiler will perform a three minute anti cycle timer delay When the request for heat has been satisfied the appliance pump and fan may continue to operate to dissipate any residual heat within the...

Страница 9: ...ume 74 litres Pre charge pressure 1 bar 2 5 Dimensions Excel 25 Excel 29 Height mm 715 Width mm 405 Depth mm 250 Dry weight kg 28 29 2 6 Clearances Excel 25 Excel 29 Sides 12mm Top 150mm from casing o...

Страница 10: ...ain pipe etc 25 mm E Below eaves 25 mm F Below balcony car port roof etc 25 mm G To the side of a soil drain pipe etc 25 mm 60mm for 80 125 5 flue H From internal external corner 25 mm 60mm for 80 125...

Страница 11: ...n vessel to accom modate the increased volume of water when the system is heated It can accept up to 8 litres of expansion from within the system generally this is sufficient however if the system has...

Страница 12: ...is to be fitted on a wall of combustible material There is no requirement to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be fitted in a timber framed building it shouldbefitte...

Страница 13: ...W PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a position at least 1 metre above the highest point in the system an...

Страница 14: ...plane see2 9 Areductionmustalsobemadetothemaximumlength see table below when additional bends are used Reduction for additional bends Bend Reduction in maximum flue length for each bend 45 bend 1 0 me...

Страница 15: ...e installation of the 80 125mm concentric flue system please refer to the instructions supplied The vertical flue terminal can be connected directly to the ap pliance flue outlet Alternatively an exte...

Страница 16: ...ir 2000mm 0225840 45 bend pair N A 0225845 90 bend pair N A 0225850 Twin bracket 5 N A 0225855 Single bracket 5 N A MOUNTING THE BOILER The fixing holes for the wall mounting bracket should now be dri...

Страница 17: ...wards the appliance 17mm per 1000mm Fig 13c Fig 14 4 6 CONNECTING THE GAS AND WATER The appliance is supplied with an accessory pack that includes service valves Theservicevalvesareforwelding Theacces...

Страница 18: ...circuits please refer to section 8 for detailed instructions ANYEXTERNALCONTROLOR WIRING MUST BE SERVED FROM THE SAME ISOLATOR AS THAT OF THE APPLIANCE The supply cable from the isolator to the appli...

Страница 19: ...d properly and in ac cordance with the instructions ensure all appliance service valves are open 5 6 INITIAL LIGHTING Ensure the electrical supply to the appliance is switched on Ensure any external c...

Страница 20: ...tres flow restrictor 5 12 FINAL CHECKS ENSURE ALL TEST NIPPLES ON THE APPLIANCE GAS VALVE ARE TIGHT AND CHECKED FOR TIGHTNESS ENSURE THE APPLIANCE FLUE SYSTEM IS FITTED CORRECTLY AND IS PROPERLY SECUR...

Страница 21: ...ved from the appliance Replace carefully in the reverse order 6 6 SAFETY VALVE fig 22 Carry out component removal procedure as described in 6 4 Disconnect the outlet pipe G from the safety valve remov...

Страница 22: ...omponent removal procedure as described in 6 4 Remove the air chamber front cover Disconnect the electrode leads and ancillary wiring from their respective connectors Re move the retaining screws V fo...

Страница 23: ...ibed in 6 4 Remove the locking pin Q1 that secures the cover R1 to the hydraulic manifold Using a hooked piece of wire carefully withdraw the by pass cartridge S1 and or DHW non return cartridge T1 En...

Страница 24: ...onnectthewiringtotheDHWflowswitch Slacken and unscrew the inlet connection Unscrew the nut E2 Lift the DHW flow switch housing from its seating If necessary remove the locking pin F2 from the DHW flow...

Страница 25: ...sed for more that 20 minutes 7 2 3 HEATING MODE With the selector switch in the heating hot water position and any additional controls time clock programmer room thermostat etc calling for heat the ap...

Страница 26: ...ut the component removal procedure as described in 6 4 You must ensure that the boiler is completely drained of water Using a suitable pressure gauge remove dust cap on expansion vessel and check the...

Страница 27: ...letion of any task that required the disconnection and re connection of any electrical wiring or component these checks must be repeated 7 8 FAULT FINDING Before attempting any faultfinding the electr...

Страница 28: ...c information on the suitability of a particular control Further guidance on the recom mended practice for the installation of external controls can be found in CHeSS HC5 HC6 www energyefficiency gov...

Страница 29: ...oiler lock out CN1 CN15 Connectors CN5 Room thermostat 24 Vdc S W CO2 function button F S 1 Flame sensor F1 Fuse 3 15A T F External fuse 3 15A F M3 Terminal strip for electrical connection hight power...

Страница 30: ...yellow led blinking gas valve maximun setting press twice burner running at maximum DHW yellow led blinking red led fixed gas valve minimum setting press three time burner running at minimum yellow l...

Страница 31: ...3 However if the CO2 reading is incorrect the minimum gas pressure must be adjusted as follows locate the minimum adjustment screw fig 37 using a suit able screwdriver remove the protection plug using...

Страница 32: ......

Страница 33: ......

Страница 34: ...to stabilise YES Is CO less than 350ppm AND CO CO2 ratio less than 0 004 NO Boiler is operating satisfactorily No further actions required Ensure test points are capped boiler case is correctly repla...

Страница 35: ......

Страница 36: ...s vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve the...

Отзывы: