background image

23

7.3 CHECKING THE CO

2

 AND ADJUSTING THE 

GAS VALVE

THE GAS VALVE MUST BE SET-UP OR ADJUSTED WITH 

THE AID OF A PROPERLY CALIBRATED FLUE GAS ANA

-

LYSER.

Isolate the appliance from the electrical supply and remove the 

appliance casing as described in 4.7.1. Restore the electrical 

supply to the boiler and switch the boiler to the OFF mode.

Have access to the printed circuit board, locate and open the 

closing plug on the dash board (L2), locate and press the CO 

button (see fig. 36 pos. SW1). Press the button the number of 

times according the function requirement as par 7.3.1.

Set  the  flue  gas  analyser  to  read  CO2,  allow  the  burner  to 

stabilise and insert the probe into the flue analysis test point 

(Y1-Z1 fig. 33). The appliance will operate in CO2 mode for 

approximately 15 minutes.

7.1 CHECKING APPLIANCE OPERATION

When carrying out any repairs or servicing to the appliance, 

the relevant commissioning procedure must be undertaken to 

ensure the continued safe operation of the appliance. Particular 

attention should be made to ensure gas tightness, water tight-

ness and the electrical integrity of the appliance.

7.2 APPLIANCE MODES OF OPERATION

NOTE

There must be sufficient system water pressure (min. 0.5 bar) 

to ensure the water pressure switch is activated. If there is in-

sufficient system pressure the pump and fan will be prevented 

from operating and the low-pressure fault code will be indicated.

7.2.1 SELECTOR SWITCH IN THE OFF/RESET POSITION

When the selector switch is in the OFF/RESET position, the 

following functions are active.

Active functions

:

• frost-protection system

• pump & actuator anti-block.

7.2.2 ON-BOARD FUNCTIONS

• 

CO FUNCTION:

 the CO function when activated, will allow the 

appliance to run at CH maximum, DHW maximum or minimum 

output whilst a combustion analysis check or a mechanical gas 

valve calibration is being carried out. Whilst the CO function 

is active, all other functions are disabled (minimum power 

operating period, anti-cycle, set-point, etc). Once enabled, 

the CO function will remain active for a 15-minute period, or 

until the function is manually deactivated 

• 

FROST-PROTECTION: 

this function is only active when 

there are no requests for heating or HW. If the temperature 

drops below 5°C, the boiler will operate on minimum power 

until the temperature of the thermistors reaches 35°C for CH 

and 55°C for DHW. Thereafter the pump & fan will over-run 

for 30-seconds.

• 

ANTI-CYCLE FUNCTION:

 the anti-cycle function ensures the 

burner remains switched off for at least 3-minutes after the 

set-point hysterisis (set-point + 5-deg) for CH heat request.  

• 

PUMP ANTI-BLOCK FUNCTION: 

when there has been no 

heating or HW request for 24-hours, the anti-block cycle is 

activated. The pump will be activated for a period of 30-sec-

onds.

• 

ACTUATOR ANTI-BLOCK FUNCTION: 

when there has been 

no heating or HW request for 24-hours, the anti-block cycle 

is activated. The divertor valve actuator will motor briefly to 

the heating position, and then back to the DHW position. The 

pump will run briefly.

• 

SARA function:

 the SARA function permits the boiler (when 

the set-point is within the SARA range) to automatically adjust 

(raise) the heating flow outlet temperature should the room 

thermostat contacts remain closed for more that 20-minutes.

7.2.3 HEATING MODE

With the selector switch in the heating  & hot water position 

and any additional controls (time clock, programmer, room 

thermostat, etc.) calling for heat, the appliance will operate 

in the heating mode. The pump and fan will be activated via 

the flow temperature sensor. When the fan is sensed to be 

operating correctly (tacho signal), the ignition sequence com-

mences. Ignition is sensed by the electronic circuit to ensure 

flame stability at the burner. Once successful ignition has been 

achieved, the electronic circuitry increases the gas rate to 75% 

for a period of 15 minutes. The speed of the fan and therefore 

the output of the boiler is determined by the temperature of the 

water sensed by the flow temperature sensor, consequently 

a high temperature at the flow sensor results in a lower fan 

speed. As the water temperature increases, the temperature 

sensors – located on the flow pipe of the boiler – reduce the 

fan speed via the electronic circuitry. Depending on the load, 

either the water temperature will continue to rise until the set 

point is achieved or the water temperature will fall whereby fan 

speed will increase relative to the output required. When the 

boiler has reached the set point (+ hysterisis), the burner will 

switch off. The built-in anti-cycle device prevents the burner from 

re-lighting for approximately 3-minutes. When the temperature 

of the flow sensor falls below the set point (- hysterisis), the 

burner will re-light.

NOTE

If the spark/sensing electrode does not sense ignition the appli-

ance will re-attempt ignition a further 4-times then go to lockout. 

When the set-point has been reached (the position of the heating 

temperature selector) as measured at the primary thermistor, the 

appliance will begin the modulation phase whereby the fan and 

gas valve will continuously modulate to maintain the set-point.

If the temperature continues to rise and exceeds the set-point 

by 5°C (hysterisis), the burner will shut down. A new ignition 

sequence will be enabled when the 3- minute anti-cycle has 

been performed and the temperature at the primary thermistor 

has dropped 5°C (hysterisis) below the set-point.

7.2.4 DHW MODE

With the selector switch in either the hot water only or heating 

& hot water position, the appliance will operate in the hot water 

mode whenever a DHW outlet is opened. A flow rate exceeding 

2-litres per minute will activate the DHW flow switch whereupon 

the pump and fan will be activated via the flow temperature 

sensor. When the fan is sensed to be operating correctly (tacho 

signal), the ignition sequence commences. Ignition is sensed 

by the electronic circuitry to ensure flame stability at the burner. 

Once successful ignition has been achieved, the electronic 

circuit allows the gas rate to achieve the modulation value.

NOTE

When the request for heating and/or hot water has been satis-

fied, the appliance pump and fan may continue to circulate to 

dissipate any residual heat within the appliance.

ATTENTION

Gas type and appliance output 

must be set 

according to the 

specific appliance specification. Vokèra accepts no responsi

-

bility if the gas type is not correctly adjusted according to the 

respective appliance specification as detailed on the appliance 

data badge.

SECTION 7 - CHECKS, ADJUSTMENTS AND FAULT FINDING

L2

Fig. 36

SW1

use the supplied 

screwdriver to push the 

CO botton (SW1)

Содержание Excel 25

Страница 1: ...S TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK Excel High ef...

Страница 2: ...3A 5 Air supply 11 3A 6 Water circulation 11 3A 7 Electrical supply 11 3A 8 Mounting on a combustible surface 11 3A 9 Timber framed buildings 11 3A 10 Inhibitors 11 3A 11 Showers 11 3A 12 Declaration...

Страница 3: ...el boiler has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and efficiency Please therefore take some ti...

Страница 4: ...et temperature or counter clockwise to reduce the temperature range 37 C 60 C Boiler at OFF standby Select this position when you want the boiler to be switched off for short periods days or if the bo...

Страница 5: ...may be necessary to reduce the flow of water at the hot water outlet tap NOTE If the appliance fails to ignite during the ignition sequence it will enter a lockout condition Should this occur please a...

Страница 6: ...switch in the bottom position To select OFF mode move the selector switch in the upper position APPLIANCE STATUS LED AND FAULT CODES Fig 3 4 WHAT IF 5 SETTING THE VOK RA Advice for homeowners Please c...

Страница 7: ...use with a sealed system only consequently they are not intended for use on open vented systems This booklet is an integral part of the appliance It is therefore necessary to ensure that the booklet...

Страница 8: ...the boiler will perform a three minute anti cycle timer delay When the request for heat has been satisfied the appliance pump and fan may continue to operate to dissipate any residual heat within the...

Страница 9: ...ume 74 litres Pre charge pressure 1 bar 2 5 Dimensions Excel 25 Excel 29 Height mm 715 Width mm 405 Depth mm 250 Dry weight kg 28 29 2 6 Clearances Excel 25 Excel 29 Sides 12mm Top 150mm from casing o...

Страница 10: ...ain pipe etc 25 mm E Below eaves 25 mm F Below balcony car port roof etc 25 mm G To the side of a soil drain pipe etc 25 mm 60mm for 80 125 5 flue H From internal external corner 25 mm 60mm for 80 125...

Страница 11: ...n vessel to accom modate the increased volume of water when the system is heated It can accept up to 8 litres of expansion from within the system generally this is sufficient however if the system has...

Страница 12: ...is to be fitted on a wall of combustible material There is no requirement to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be fitted in a timber framed building it shouldbefitte...

Страница 13: ...W PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a position at least 1 metre above the highest point in the system an...

Страница 14: ...plane see2 9 Areductionmustalsobemadetothemaximumlength see table below when additional bends are used Reduction for additional bends Bend Reduction in maximum flue length for each bend 45 bend 1 0 me...

Страница 15: ...e installation of the 80 125mm concentric flue system please refer to the instructions supplied The vertical flue terminal can be connected directly to the ap pliance flue outlet Alternatively an exte...

Страница 16: ...ir 2000mm 0225840 45 bend pair N A 0225845 90 bend pair N A 0225850 Twin bracket 5 N A 0225855 Single bracket 5 N A MOUNTING THE BOILER The fixing holes for the wall mounting bracket should now be dri...

Страница 17: ...wards the appliance 17mm per 1000mm Fig 13c Fig 14 4 6 CONNECTING THE GAS AND WATER The appliance is supplied with an accessory pack that includes service valves Theservicevalvesareforwelding Theacces...

Страница 18: ...circuits please refer to section 8 for detailed instructions ANYEXTERNALCONTROLOR WIRING MUST BE SERVED FROM THE SAME ISOLATOR AS THAT OF THE APPLIANCE The supply cable from the isolator to the appli...

Страница 19: ...d properly and in ac cordance with the instructions ensure all appliance service valves are open 5 6 INITIAL LIGHTING Ensure the electrical supply to the appliance is switched on Ensure any external c...

Страница 20: ...tres flow restrictor 5 12 FINAL CHECKS ENSURE ALL TEST NIPPLES ON THE APPLIANCE GAS VALVE ARE TIGHT AND CHECKED FOR TIGHTNESS ENSURE THE APPLIANCE FLUE SYSTEM IS FITTED CORRECTLY AND IS PROPERLY SECUR...

Страница 21: ...ved from the appliance Replace carefully in the reverse order 6 6 SAFETY VALVE fig 22 Carry out component removal procedure as described in 6 4 Disconnect the outlet pipe G from the safety valve remov...

Страница 22: ...omponent removal procedure as described in 6 4 Remove the air chamber front cover Disconnect the electrode leads and ancillary wiring from their respective connectors Re move the retaining screws V fo...

Страница 23: ...ibed in 6 4 Remove the locking pin Q1 that secures the cover R1 to the hydraulic manifold Using a hooked piece of wire carefully withdraw the by pass cartridge S1 and or DHW non return cartridge T1 En...

Страница 24: ...onnectthewiringtotheDHWflowswitch Slacken and unscrew the inlet connection Unscrew the nut E2 Lift the DHW flow switch housing from its seating If necessary remove the locking pin F2 from the DHW flow...

Страница 25: ...sed for more that 20 minutes 7 2 3 HEATING MODE With the selector switch in the heating hot water position and any additional controls time clock programmer room thermostat etc calling for heat the ap...

Страница 26: ...ut the component removal procedure as described in 6 4 You must ensure that the boiler is completely drained of water Using a suitable pressure gauge remove dust cap on expansion vessel and check the...

Страница 27: ...letion of any task that required the disconnection and re connection of any electrical wiring or component these checks must be repeated 7 8 FAULT FINDING Before attempting any faultfinding the electr...

Страница 28: ...c information on the suitability of a particular control Further guidance on the recom mended practice for the installation of external controls can be found in CHeSS HC5 HC6 www energyefficiency gov...

Страница 29: ...oiler lock out CN1 CN15 Connectors CN5 Room thermostat 24 Vdc S W CO2 function button F S 1 Flame sensor F1 Fuse 3 15A T F External fuse 3 15A F M3 Terminal strip for electrical connection hight power...

Страница 30: ...yellow led blinking gas valve maximun setting press twice burner running at maximum DHW yellow led blinking red led fixed gas valve minimum setting press three time burner running at minimum yellow l...

Страница 31: ...3 However if the CO2 reading is incorrect the minimum gas pressure must be adjusted as follows locate the minimum adjustment screw fig 37 using a suit able screwdriver remove the protection plug using...

Страница 32: ......

Страница 33: ......

Страница 34: ...to stabilise YES Is CO less than 350ppm AND CO CO2 ratio less than 0 004 NO Boiler is operating satisfactorily No further actions required Ensure test points are capped boiler case is correctly repla...

Страница 35: ......

Страница 36: ...s vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve the...

Отзывы: