background image

32

COMMISSIONING: CO AND COMBUSTION RATIO CHECK

 

 

 

 

 

 

 

 

 

CO AND COMBUSTION 
RATIO CHECK  
First verify that flue 
integrity has been 
visually checked in 
accordance with the 
“Before CO and 
combustion ratio check” 
box (above) before 
proceeding to the “Check 
CO and combustion ratio 
at maximum rate” stage. 

SET BOILER TO MAXIMUM 

RATE 

In accordance with section 7.3-

7.4, set boiler to operate at 

maximum rate (full load 

condition). Allow sufficient 

time for combustion to 

stabilise. 

CHECK CO AND COMBUSTION 

RATIO AT MAXIMUM RATE 

With boiler still set at maximum 

rate, insert analyser probe into 

flue gas sampling point. Allow 

readings to stabilise before 

recording. 

 

Is CO less than 

350ppm AND 

CO/CO2 ratio 

less than 0.004? 

NO 

Check all seals around the 

appliance burner, internal flue 

seals, door and case seals. 

Rectify where necessary. 

Is CO less than 

350ppm AND 

CO/CO2 ratio 

less than 0.004? 

CHECK CO AND 

COMBUSTION RATIO AT 

MINIMUM RATE 

With boiler set at minimum 

rate, insert analyser probe 

into flue gas sampling point. 

Allow readings to stabilise 

before recording. 

 

YES 

Turn off appliance and 

call Vokera technical 

helpline for advice. 

The appliance must not 

be commissioned until 

problems are identified 

and resolved. If 

commissioning cannot be 

fully completed, the 

appliance must be 

disconnected from the 

gas supply in accordance 

with the GSIUR. 

NOTE: Check and record CO 
and combustion ratio at both 
maximum AND minimum 
rate before contacting 
Vokera technical.
 

SET BOILER TO MINIMUM RATE 

In accordance with section 7.3-

7.4, set boiler to operate at 

minimum rate (to minimum 

load condition). Allow sufficient 

time for combustion to stabilise. 

 

YES 

Is CO less than 

350ppm AND 

CO/CO2 ratio less 

than 0.004? 

NO 

Boiler is operating satisfactorily 

No further actions required. 

Ensure test points are capped, boiler case is correctly replaced and all other commissioning procedures are completed. 

Complete Benchmark Checklist, recording CO and combustion ratio readings as required

NOTE 

The air/gas ratio valve is factory-set and 
must not be adjusted during commissioning 
unless this action is recommended, following 
contact with Vokera technical. If any such 
adjustment is recommended and further 
checking of the boiler is required, the 
engineer must be competent to carry out 
this work and to use the flue gas analyser 
accordingly. If the boiler requires conversion 
to operate with a different gas family (e.g., 
conversion from natural gas to LPG) separate 
guidance will be provided by Vokera 
technical and must be followed. 

NO 

YES 

BEFORE CO AND COMBUSTION RATIO CHECK 

The boiler installation instructions should have been followed, 

gas type verified and gas supply pressure/rate checked as 

required prior to commissioning. 

As part of the installation process, ESPECIALLY WHERE A FLUE 

HAS BEEN FITTED BY PERSONS OTHER THAN THE BOILER 

INSTALLER, visually check the integrity of the whole flue 

system to confirm that all components are correctly 

assembled, fixed and supported. Check that the maximum flue 

lengths have not been exceeded and all guidance has been 

followed (e.g. Technical Bulletin 008). 

The flue gas analyser should be of the correct type, as specified 

by BS 7967. 

Before use, the flue gas analyser should have been maintained 

and calibrated as specified by the manufacturer. The installer 

must have the relevant competence for use of the analyser. 

Check and zero the analyser IN FRESH AIR, as per analyser 

manufacturer’s instructions. 

Содержание Excel 25

Страница 1: ...S TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK Excel High ef...

Страница 2: ...3A 5 Air supply 11 3A 6 Water circulation 11 3A 7 Electrical supply 11 3A 8 Mounting on a combustible surface 11 3A 9 Timber framed buildings 11 3A 10 Inhibitors 11 3A 11 Showers 11 3A 12 Declaration...

Страница 3: ...el boiler has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and efficiency Please therefore take some ti...

Страница 4: ...et temperature or counter clockwise to reduce the temperature range 37 C 60 C Boiler at OFF standby Select this position when you want the boiler to be switched off for short periods days or if the bo...

Страница 5: ...may be necessary to reduce the flow of water at the hot water outlet tap NOTE If the appliance fails to ignite during the ignition sequence it will enter a lockout condition Should this occur please a...

Страница 6: ...switch in the bottom position To select OFF mode move the selector switch in the upper position APPLIANCE STATUS LED AND FAULT CODES Fig 3 4 WHAT IF 5 SETTING THE VOK RA Advice for homeowners Please c...

Страница 7: ...use with a sealed system only consequently they are not intended for use on open vented systems This booklet is an integral part of the appliance It is therefore necessary to ensure that the booklet...

Страница 8: ...the boiler will perform a three minute anti cycle timer delay When the request for heat has been satisfied the appliance pump and fan may continue to operate to dissipate any residual heat within the...

Страница 9: ...ume 74 litres Pre charge pressure 1 bar 2 5 Dimensions Excel 25 Excel 29 Height mm 715 Width mm 405 Depth mm 250 Dry weight kg 28 29 2 6 Clearances Excel 25 Excel 29 Sides 12mm Top 150mm from casing o...

Страница 10: ...ain pipe etc 25 mm E Below eaves 25 mm F Below balcony car port roof etc 25 mm G To the side of a soil drain pipe etc 25 mm 60mm for 80 125 5 flue H From internal external corner 25 mm 60mm for 80 125...

Страница 11: ...n vessel to accom modate the increased volume of water when the system is heated It can accept up to 8 litres of expansion from within the system generally this is sufficient however if the system has...

Страница 12: ...is to be fitted on a wall of combustible material There is no requirement to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be fitted in a timber framed building it shouldbefitte...

Страница 13: ...W PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a position at least 1 metre above the highest point in the system an...

Страница 14: ...plane see2 9 Areductionmustalsobemadetothemaximumlength see table below when additional bends are used Reduction for additional bends Bend Reduction in maximum flue length for each bend 45 bend 1 0 me...

Страница 15: ...e installation of the 80 125mm concentric flue system please refer to the instructions supplied The vertical flue terminal can be connected directly to the ap pliance flue outlet Alternatively an exte...

Страница 16: ...ir 2000mm 0225840 45 bend pair N A 0225845 90 bend pair N A 0225850 Twin bracket 5 N A 0225855 Single bracket 5 N A MOUNTING THE BOILER The fixing holes for the wall mounting bracket should now be dri...

Страница 17: ...wards the appliance 17mm per 1000mm Fig 13c Fig 14 4 6 CONNECTING THE GAS AND WATER The appliance is supplied with an accessory pack that includes service valves Theservicevalvesareforwelding Theacces...

Страница 18: ...circuits please refer to section 8 for detailed instructions ANYEXTERNALCONTROLOR WIRING MUST BE SERVED FROM THE SAME ISOLATOR AS THAT OF THE APPLIANCE The supply cable from the isolator to the appli...

Страница 19: ...d properly and in ac cordance with the instructions ensure all appliance service valves are open 5 6 INITIAL LIGHTING Ensure the electrical supply to the appliance is switched on Ensure any external c...

Страница 20: ...tres flow restrictor 5 12 FINAL CHECKS ENSURE ALL TEST NIPPLES ON THE APPLIANCE GAS VALVE ARE TIGHT AND CHECKED FOR TIGHTNESS ENSURE THE APPLIANCE FLUE SYSTEM IS FITTED CORRECTLY AND IS PROPERLY SECUR...

Страница 21: ...ved from the appliance Replace carefully in the reverse order 6 6 SAFETY VALVE fig 22 Carry out component removal procedure as described in 6 4 Disconnect the outlet pipe G from the safety valve remov...

Страница 22: ...omponent removal procedure as described in 6 4 Remove the air chamber front cover Disconnect the electrode leads and ancillary wiring from their respective connectors Re move the retaining screws V fo...

Страница 23: ...ibed in 6 4 Remove the locking pin Q1 that secures the cover R1 to the hydraulic manifold Using a hooked piece of wire carefully withdraw the by pass cartridge S1 and or DHW non return cartridge T1 En...

Страница 24: ...onnectthewiringtotheDHWflowswitch Slacken and unscrew the inlet connection Unscrew the nut E2 Lift the DHW flow switch housing from its seating If necessary remove the locking pin F2 from the DHW flow...

Страница 25: ...sed for more that 20 minutes 7 2 3 HEATING MODE With the selector switch in the heating hot water position and any additional controls time clock programmer room thermostat etc calling for heat the ap...

Страница 26: ...ut the component removal procedure as described in 6 4 You must ensure that the boiler is completely drained of water Using a suitable pressure gauge remove dust cap on expansion vessel and check the...

Страница 27: ...letion of any task that required the disconnection and re connection of any electrical wiring or component these checks must be repeated 7 8 FAULT FINDING Before attempting any faultfinding the electr...

Страница 28: ...c information on the suitability of a particular control Further guidance on the recom mended practice for the installation of external controls can be found in CHeSS HC5 HC6 www energyefficiency gov...

Страница 29: ...oiler lock out CN1 CN15 Connectors CN5 Room thermostat 24 Vdc S W CO2 function button F S 1 Flame sensor F1 Fuse 3 15A T F External fuse 3 15A F M3 Terminal strip for electrical connection hight power...

Страница 30: ...yellow led blinking gas valve maximun setting press twice burner running at maximum DHW yellow led blinking red led fixed gas valve minimum setting press three time burner running at minimum yellow l...

Страница 31: ...3 However if the CO2 reading is incorrect the minimum gas pressure must be adjusted as follows locate the minimum adjustment screw fig 37 using a suit able screwdriver remove the protection plug using...

Страница 32: ......

Страница 33: ......

Страница 34: ...to stabilise YES Is CO less than 350ppm AND CO CO2 ratio less than 0 004 NO Boiler is operating satisfactorily No further actions required Ensure test points are capped boiler case is correctly repla...

Страница 35: ......

Страница 36: ...s vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve the...

Отзывы: