background image

24

fig. 37

7.3.2 GAS VALVE MAXIMUM SETTING

Set the CO

2

 button at maximum (see 7.3.1), once the maximum 

is obtained check that it corresponds with the appropriate CO

2

 

value (Maximum) for the respective appliance (see 2.11). If 

the CO

2

 reading is correct, proceed to gas valve minimum 

setting (7.3.3).

However, if the CO

2

 reading is incorrect, the maximum gas 

pressure must be adjusted as follows:

•  using a 2.5mm Allen key, very slowly turn the maximum ad

-

justment screw (see fig. 37) – clockwise to decrease, counter 

clockwise to increase – until the correct value is displayed on 

the CO

2

 analyser (allow time for the analyser to stabilise).

7.3.3 GAS VALVE MINIMUM SETTING

Set the CO

2

 button at minimum (see 7.3.1), once the minimum 

is obtained check that it corresponds with the appropriate CO

2

 

value (Minimum) for the respective appliance (see 2.11). If the 

CO

2

 reading is correct, proceed to completion (7.3.4).

However, if the CO

2

 reading is incorrect, the minimum gas 

pressure must be adjusted as follows:

•  locate the minimum adjustment screw (fig. 37), 

using a suit-

able screwdriver remove the protection plug 

•  using a 4mm Allen key, very slowly turn the minimum adjust

-

ment  screw  (see  fig.  37)  -  clockwise  to  increase,  counter 

clockwise to decrease - until the correct value is displayed 

on the CO

2

 analyser (allow time for the analyser to stabilise).

7.3.4 COMPLETION

On completion of the combustion analysis check and/or any 

gas valve adjustment, refit the plug (fig. 36 

L2) 

and move the 

mode selector throught 

 position.  Remove the test probe 

from the test point and refit the sealing screw/s and/or cap. 

IMPORTANT

A GAS TIGHTNESS CHECK MUST BE CARRIED OUT IF ANY 

GAS CARRYING COMPONENTS HAVE BEEN REMOVED, 

REPLACED OR DISTURBED.

7.4 COMBUSTION ANALYSIS TEST

A combustion analysis check can easily be carried out on the 

appliance via the test points located on the top of the applian-

ce (see 7.3).

•  Operate the boiler in combustion analysis mode (see 7.3.1)

•  Insert the flue gas analyser probe into the flue gas test point 

(see fig. 33) and compare the values with those shown in 

section 2 (Nat. Gas) or section 10 (LPG). If different adjust 

the gas valve according to 7.3.1, 7.3.2, & 7.3.3.

The appliance will operate in CO2 mode for approximately 

15minutes.

Note

: If a measured CO/CO2 ratio of 0.004/1 or less AND a 

CO reading of less than 350ppm cannot be achieved, please 

contact Vokera technical for advice.

7.5 CHECKING THE EXPANSION VESSEL

Carry out the component removal procedure as described in 

6.4. You must ensure that the boiler is completely drained of 

water. Using a suitable pressure gauge, remove dust cap on 

expansion vessel and check the charge pressure.  The cor-

rect charge pressure should be 1.0 bar ± 0.1 bar. If the charge 

pressure is less, use a suitable pump to increase the charge.

7.3.1 CO

2

 FUNCTION SETTINGS

Locate the CO

 

button (see 7.3)

Select the main selector switch in position 

CO

2

 FUNCTIONS 

ACTION ON THE BUTTON 

LED STATUS

combustion analysis mode 

press once = burner running at maximum heating 

yellow led blinking

gas valve maximun setting 

press twice = burner running at maximum DHW 

yellow led bl red led fixed

gas valve minimum setting 

press three time = burner running at minimum 

yellow led bl green led fixed

NOTE

1 - Any additional pressing of CO

 

button after the third time the burner switched between maximum DHW and minimum.

2 - To restart the CO

 

function it is necessary to pass throught the 

 position with the main selector switch

NOTE

You must ensure the drain valve is in the open position whilst 

re-charging takes place. Replace the dust cap and carry out 

the relevant commissioning procedure (section 5).

7.6 EXTERNAL FAULTS

Before carrying out any faultfinding or component replacement, 

ensure the fault is not attributable to any aspect of the installation.

7.6.1 INSTALLATION FAULTS
 Symptom 

Possible cause 

 No led/ignition 

Check wiring/check electrical  

 supply 

 No hot water 

Check pipe-work 

 No heating  

Check external controls 

 Fault   

Possible cause 

 

Red led fixed

 

Check gas supply, check flue  

 

system, check polarity 

7.7 ELECTRICAL CHECKS

Any electrical checks must be carried out by a suitably quali-

fied person.

7.7.1 EARTH CONTINUITY TEST

Isolate the appliance from the electrical supply, and using a 

suitable multi-meter carry out a resistance test. Connect test 

leads between an appliance earth point and the earth wire of 

the appliance supply cable. The resistance should be less than 

1 OHM. If the resistance is greater than 1 OHM check all earth 

wires and connectors for continuity and integrity.

7.7.2 SHORT CIRCUIT CHECK

Isolate the appliance from the electrical supply, and using a 

suitable multi-meter, carry out a short circuit test between the 

Live & Neutral connections at the appliance terminal strip. 

Repeat above test on the Live & Earth connections at the ap

-

pliance terminal strip.

NOTE

Should it be found that the fuse has failed but no fault is in-

dicated, a detailed continuity check will be required to trace 

Minimum 

screw

Inlet gas pressure

connection

Compensation pipe 

connection

Maximum 

screw

Содержание Excel 25

Страница 1: ...S TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK Excel High ef...

Страница 2: ...3A 5 Air supply 11 3A 6 Water circulation 11 3A 7 Electrical supply 11 3A 8 Mounting on a combustible surface 11 3A 9 Timber framed buildings 11 3A 10 Inhibitors 11 3A 11 Showers 11 3A 12 Declaration...

Страница 3: ...el boiler has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and efficiency Please therefore take some ti...

Страница 4: ...et temperature or counter clockwise to reduce the temperature range 37 C 60 C Boiler at OFF standby Select this position when you want the boiler to be switched off for short periods days or if the bo...

Страница 5: ...may be necessary to reduce the flow of water at the hot water outlet tap NOTE If the appliance fails to ignite during the ignition sequence it will enter a lockout condition Should this occur please a...

Страница 6: ...switch in the bottom position To select OFF mode move the selector switch in the upper position APPLIANCE STATUS LED AND FAULT CODES Fig 3 4 WHAT IF 5 SETTING THE VOK RA Advice for homeowners Please c...

Страница 7: ...use with a sealed system only consequently they are not intended for use on open vented systems This booklet is an integral part of the appliance It is therefore necessary to ensure that the booklet...

Страница 8: ...the boiler will perform a three minute anti cycle timer delay When the request for heat has been satisfied the appliance pump and fan may continue to operate to dissipate any residual heat within the...

Страница 9: ...ume 74 litres Pre charge pressure 1 bar 2 5 Dimensions Excel 25 Excel 29 Height mm 715 Width mm 405 Depth mm 250 Dry weight kg 28 29 2 6 Clearances Excel 25 Excel 29 Sides 12mm Top 150mm from casing o...

Страница 10: ...ain pipe etc 25 mm E Below eaves 25 mm F Below balcony car port roof etc 25 mm G To the side of a soil drain pipe etc 25 mm 60mm for 80 125 5 flue H From internal external corner 25 mm 60mm for 80 125...

Страница 11: ...n vessel to accom modate the increased volume of water when the system is heated It can accept up to 8 litres of expansion from within the system generally this is sufficient however if the system has...

Страница 12: ...is to be fitted on a wall of combustible material There is no requirement to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be fitted in a timber framed building it shouldbefitte...

Страница 13: ...W PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a position at least 1 metre above the highest point in the system an...

Страница 14: ...plane see2 9 Areductionmustalsobemadetothemaximumlength see table below when additional bends are used Reduction for additional bends Bend Reduction in maximum flue length for each bend 45 bend 1 0 me...

Страница 15: ...e installation of the 80 125mm concentric flue system please refer to the instructions supplied The vertical flue terminal can be connected directly to the ap pliance flue outlet Alternatively an exte...

Страница 16: ...ir 2000mm 0225840 45 bend pair N A 0225845 90 bend pair N A 0225850 Twin bracket 5 N A 0225855 Single bracket 5 N A MOUNTING THE BOILER The fixing holes for the wall mounting bracket should now be dri...

Страница 17: ...wards the appliance 17mm per 1000mm Fig 13c Fig 14 4 6 CONNECTING THE GAS AND WATER The appliance is supplied with an accessory pack that includes service valves Theservicevalvesareforwelding Theacces...

Страница 18: ...circuits please refer to section 8 for detailed instructions ANYEXTERNALCONTROLOR WIRING MUST BE SERVED FROM THE SAME ISOLATOR AS THAT OF THE APPLIANCE The supply cable from the isolator to the appli...

Страница 19: ...d properly and in ac cordance with the instructions ensure all appliance service valves are open 5 6 INITIAL LIGHTING Ensure the electrical supply to the appliance is switched on Ensure any external c...

Страница 20: ...tres flow restrictor 5 12 FINAL CHECKS ENSURE ALL TEST NIPPLES ON THE APPLIANCE GAS VALVE ARE TIGHT AND CHECKED FOR TIGHTNESS ENSURE THE APPLIANCE FLUE SYSTEM IS FITTED CORRECTLY AND IS PROPERLY SECUR...

Страница 21: ...ved from the appliance Replace carefully in the reverse order 6 6 SAFETY VALVE fig 22 Carry out component removal procedure as described in 6 4 Disconnect the outlet pipe G from the safety valve remov...

Страница 22: ...omponent removal procedure as described in 6 4 Remove the air chamber front cover Disconnect the electrode leads and ancillary wiring from their respective connectors Re move the retaining screws V fo...

Страница 23: ...ibed in 6 4 Remove the locking pin Q1 that secures the cover R1 to the hydraulic manifold Using a hooked piece of wire carefully withdraw the by pass cartridge S1 and or DHW non return cartridge T1 En...

Страница 24: ...onnectthewiringtotheDHWflowswitch Slacken and unscrew the inlet connection Unscrew the nut E2 Lift the DHW flow switch housing from its seating If necessary remove the locking pin F2 from the DHW flow...

Страница 25: ...sed for more that 20 minutes 7 2 3 HEATING MODE With the selector switch in the heating hot water position and any additional controls time clock programmer room thermostat etc calling for heat the ap...

Страница 26: ...ut the component removal procedure as described in 6 4 You must ensure that the boiler is completely drained of water Using a suitable pressure gauge remove dust cap on expansion vessel and check the...

Страница 27: ...letion of any task that required the disconnection and re connection of any electrical wiring or component these checks must be repeated 7 8 FAULT FINDING Before attempting any faultfinding the electr...

Страница 28: ...c information on the suitability of a particular control Further guidance on the recom mended practice for the installation of external controls can be found in CHeSS HC5 HC6 www energyefficiency gov...

Страница 29: ...oiler lock out CN1 CN15 Connectors CN5 Room thermostat 24 Vdc S W CO2 function button F S 1 Flame sensor F1 Fuse 3 15A T F External fuse 3 15A F M3 Terminal strip for electrical connection hight power...

Страница 30: ...yellow led blinking gas valve maximun setting press twice burner running at maximum DHW yellow led blinking red led fixed gas valve minimum setting press three time burner running at minimum yellow l...

Страница 31: ...3 However if the CO2 reading is incorrect the minimum gas pressure must be adjusted as follows locate the minimum adjustment screw fig 37 using a suit able screwdriver remove the protection plug using...

Страница 32: ......

Страница 33: ......

Страница 34: ...to stabilise YES Is CO less than 350ppm AND CO CO2 ratio less than 0 004 NO Boiler is operating satisfactorily No further actions required Ensure test points are capped boiler case is correctly repla...

Страница 35: ......

Страница 36: ...s vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve the...

Отзывы: