Request SMS
Test is in progress requesting server to send SMS
Wait for SMS
Test is in progress waiting to receive SMS from server
3.9.5 Testing the Broadband/PowerLink Module
The Broadband diagnostic procedure enables to test the communication of the Broadband Module (see section 3.6.8)
with the PowerManage server and reports the diagnostic result. In case of communication failure, detailed information of
the failure is reported.
07:DIAGNOSTICS
⋅ ⋅ ⋅
BROADBAND MODULE
⋅ ⋅ ⋅
PLEASE WAIT… Unit is OK
Notes:
1.
When the
button is pressed, the test result may take up to 4 min. before it is displayed.
2.
If the Broadband Module is not registered to the PowerMaster, the menu "BROADBAND MODULE" will not be
displayed.
The following table presents the list of messages that may be reported:
Message
Description
BROADBAND MODULE
UNIT IS OK
Broadband Module is functioning correctly.
BROADBAND MODULE
TEST ABORTED
The diagnostic test is aborted, as follows:
•
AC failure – Broadband Module is set to OFF mode.
•
Broadband Module has not completed the power-up procedure. In this case, the
installer should wait a maximum of 30 seconds before re-testing.
BROADBAND MODULE
COM. LOSS
The RS-232 serial interface between the Broadband Module and the PowerMaster failed.
BROADBAND MODULE
BBA RCVR IP MISS
Receivers IP 1 and 2 settings are missing in the PowerMaster.
BROADBAND MODULE
CABLE UNPLUGGED
The Ethernet cable is not connected to the Broadband Module.
BROADBAND MODULE
Check lan config
This message appears in any of the following cases:
•
Incorrect Broadband Module IP has been entered.
•
Incorrect subnet mask has been entered.
•
Incorrect default gateway has been entered.
•
DHCP server failure.
BROADBAND MODULE
RCVR#1 UNREACH
Receiver 1 or 2 is inaccessible, as follows:
•
Wrong receiver IP has been entered.
•
Receiver failure.
•
WAN Network failure.
BROADBAND MODULE
RCVR#2 UNREACH
BROADBAND MODULE
The PowerMaster unit is not registered to IP receiver 1 or 2.
D-306919 KP-250 PG2 Installer’s Guide