GSM KEEP ALIVE
every 28 days
Some GSM Service providers tend to disconnect the GSM connection if the user has not
initiated any outgoing telephone calls during the last 28 days.
To prevent from disconnecting the GSM connection, you can configure the system to generate
a "keep alive" GSM call every 28 days sending a test message either to the first SMS number
(if exists) or alternatively first private telephone number.
TRANS PROTOCOL
TCP
Select the type of protocol used by the control panel to transfer data over the internet.
Options:
TCP
or
UDP.
Note:
A change of option should be performed in coordination with tech support.
3.6.4 Configuring Events Reporting to Monitoring Stations
The PowerMaster control panel is designed to report alarm, alerts, troubles and other events and messages to two
Monitoring Stations C.S.1 and C.S.2 via PSTN telephone line, Cellular i.e. GSM voice (analog), GPRS (IP) & SMS or
Broadband IP communications channels. In this section, you configure and define all parameters and features required
for the reporting of the event messages to Monitoring Stations such as:
•
The events reported to each of the two Monitoring Stations C.S.1 and C.S.2 and corresponding backups.
•
The communication means (channel) used for the reporting and the backup means (channel) in case of failure.
•
The customer's (subscriber) account number(s) to be reported to each monitoring station.
•
The telephone numbers, IP addresses and SMS numbers and reporting formats of the corresponding alarm receivers
at the two Monitoring Stations C.S.1 and C.S.2 and the number of reporting retry attempts in case of failure to report.
•
The communication Auto Tests and communication Fail reports.
•
The reporting of certain system function events such as "Confirmed Alarm", "Recent Close", Zone Restore" and
"System Not-Used".
04:COMMUNICATION
⋅⋅⋅
3:C.S.REPORTING
⋅⋅⋅
MENU you wish
Enter "
3:C.S.REPORTING
", select the menu you wish to configure (see guidance above and in section 3.6.1), then refer
to the table below which provides you with detailed explanations and configuration instructions for each option.
Option and default
Configuration Instructions
01:RPRT EVENTS
all-o/c
∗
backup
Define which events (i.e.
Alarms (alrm)
;
Open/close (o/c)
;
Alerts (alrt)
;
All events (all)
;
Maintenance
and
Troubles
) will be reported to the Monitoring Stations.
The minus (-) symbol means "less/except" e.g.
all(-alrt)
means
all
events except
alerts
.
The asterisk (
) is a separator between events reported to
Monitoring Station 1
(C.S.1) and
events reported to
Monitoring Station 2
(C.S.2). For detailed and more complete explanation
see the "
Event Reporting Chart
" at the end of this section.
Options:
all-o/c
backup
all-o/c
o/c
disable report
all
all
all(-alrt)
alrt
all
backup
all-o/c
all-o/c
alrm
all(-alrm)
Note:
Alarm events (
alrm
) have highest priority and Alert events (
alrt
) have lowest
priority.
02:1st RPRT CHAN
disabled
If the system is equipped also with Cellular communicators, you must define which of the
communicating channels (i.e. Cellular or PSTN) the system will use as the main channel (i.e. 1
st
priority) for reporting event messages to Monitoring Stations, and if the main channel fails, which
channels will be used for the 2
nd
and 3
rd
reporting priorities.
Enter the "1
st
RPRT CHAN"; option and define which of the communication channels the system
will use as the main reporting channel. To define also backup reporting channels, enter the "2nd
RPRT CHAN" and "3rd RPRT CHAN" options and define them as well.
03:2nd RPRT CHAN
disabled
04:3rd RPRT CHAN
disabled
D-306919 KP-250 PG2 Installer’s Guide
43