03:Option and default
Configuration Instructions
Options:
off
and
on
.
Note:
To enable the reporting, you must configure the system to report "alrt" events to
Private users (Latchkey belongs to the "alerts" group of events). Refer to section 3.6.5
"
REPORTED EVENTS
" option in both "
VOICE REPORT
" & "
SMS REPORT
" menus.
08:DISARM OPTION
any time
Certain regulations require that when the system is armed in AWAY mode, it may not
be disarmed from the outside of the house (such as by keyfobs) before entering the
protected premises and activating an "Entry Delay" zone. To answer this requirement,
the KP-250 PG2 provides you with the following configurable options to disarm the
system:
A:
At "
any time
", the system can be disarmed at all times from all devices.
B:
During entry delay, the system can be disarmed only using keyfob or prox
operated devices ("
on entry wrless
"
)
.
C:
During entry delay by code, the system can be disarmed only using the KP-250
PG2 keypad ("
entry + away kp.
").
D:
During entry delay, the system can be disarmed using keyfobs or by code using
the KP-250 PG2 keypad ("
on entry all.
").
Note:
In some PowerMaster variants, this menu is displayed in the Operation Mode only.
09:ARMING KEY
Arm AWAY
Determine that, when activated, the Arming Key will arm AWAY or HOME.
Options:
arm AWAY
and
arm HOME
.
3.5.3 Configuring Zones Functionality
The following table provides you with a detailed description of each option and its configuration settings. To select an
option and change its configuration – refer to section 3.5.1.
Option and default
Configuration Instructions
21:SWINGER STOP
after 1 alarm
Define the number of times a zone is allowed to initiate an alarm within a single
arming/disarming period (including tamper & power failure events of detectors, etc.). If the
number of alarms from a specific zone exceeds the programmed number, the KP-250 PG2
automatically bypasses the zone to prevent recurrent siren noise and excessive reporting
to the Monitoring Station. The zone will be reactivated upon disarming, or 48 hours after
having been bypassed (if the system remains armed).
Options:
after 1 alarm
;
after 2 alarms
(default in USA);
after 3 alarms
and
no stop
.
Notes:
1. If swinger stop is enabled, a soak fail event will not be triggered.
2. When a detector is in Soak Test mode and also set to bypass, Swinger Stop will not
prevent the sending of events. This may result in excessive reporting of Soak Fail
events.
22:CROSS ZONING
off
Define whether cross zoning will be active "
on
" or inactive "
off
". Cross zoning is a method
used to counteract false alarms - an alarm will be initiated only when two adjacent zones
(zone couples) are violated within a 30-second time window.
This feature is active only when the system is armed AWAY and only with respect to the
following zone couples: 18+19, 20+21, 22+23, 24+25, 26+27 (PowerMaster-10 G2
system) / 40+41, 42+43, 44+45, 46+47, 48+49, 50+51, 52+53, 54+55, 56+57, 58+59,
60+61, 62+63 (PowerMaster-30 G2 / PowerMaster-33 G2 system).
Notes:
1. If one of the two crossed zones is bypassed (see Section 3.5.2), the remaining
zone will function independently.