Rated voltage:
230 V~
Rated frequency:
50 Hz
Rated current:
6.0 A
Safety class:
I
Protection:
IP X 4 D to
EN 60529
Permissible ambient temperature
&
during operation:
0 to +40 °C
&
during storage
and transport:
-20 to +65 °C
Electronic tempera-
ture limiter setting:
82 °C (fixed)
Temperature limiter
setting:
100 °C (fixed)
Line fuse (mains):
max. 16 A
Gas fired boiler, category I
2N
Rated output range T
V
/T
R
50/
30 °C
kW
30 - 80
30 - 105
Rated thermal load range
kW
28.1 - 75.0
28.1 - 98.5
Power consumption
(max.)
W
105
150
Connection values
in relation to the max. load
with
Natural gas E
m
3
/h
7.94
10.42
Natural gas LL
m
3
/h
9.23
12.12
Product ID
_
-0085 BR 0432
Note
The supply values are only for documentation purposes (e.g. in the gas contract
application) or to estimate the supplementary volumetric settings. Because of
factory settings, the gas pressure must not be altered from these settings.
Reference: 15 °C, 1013 mbar.
Specification
113
Specification
5692
761
GB
Содержание Vitodens 200-W WB2B Series
Страница 105: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 105 Designs 5692 761 GB...
Страница 109: ...Parts lists cont 109 Parts lists 5692 761 GB...
Страница 110: ...Parts lists cont 110 Parts lists 5692 761 GB...
Страница 111: ...Parts lists cont 111 Parts lists 5692 761 GB...
Страница 118: ...118 5692 761 GB...
Страница 119: ...119 5692 761 GB...