Function area
Coding addresses
System design
00
Boiler/burner
06 to 54
DHW
56 to 73
General
76 to 9F
Heating circuit A1 (heating circuit without
mixer)
A0 to Fb
Heating circuit with mixer M2
A0 to Fb
Note
Heating systems with one heating circuit without mixer and one heating circuit
with mixer:
Initially, the possible coding addresses "A0" to "Fb" for the heating circuit with-
out mixer A1 are scanned; then the coding addresses for the heating circuit with
mixer M2 are scanned.
Coding
Coding in the delivered condition
Possible change
System design
00 :1
System version 1 and 3:
1 heating circuit without
mixer A1, without DHW
heating
00 :2
System version 1 and 3:
1 heating circuit without
mixer A1, with DHW heat-
ing
00 :3
System version 2:
1 heating circuit with
mixer M2, without DHW
heating
00 :4
System version 2:
1 heating circuit with
mixer M2, with DHW
heating
00 :5
System version 2:
1 heating circuit without
mixer A1; 1 heating cir-
cuit with mixer M2, with-
out DHW heating
00 :6
System version 2:
1 heating circuit without
mixer A1; 1 heating cir-
cuit with mixer M2, with
DHW heating
Code 2
(cont.)
40
Coding
5692
761
GB
Содержание Vitodens 200-W WB2B Series
Страница 105: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 105 Designs 5692 761 GB...
Страница 109: ...Parts lists cont 109 Parts lists 5692 761 GB...
Страница 110: ...Parts lists cont 110 Parts lists 5692 761 GB...
Страница 111: ...Parts lists cont 111 Parts lists 5692 761 GB...
Страница 118: ...118 5692 761 GB...
Страница 119: ...119 5692 761 GB...