Coding in the delivered condition
Possible change
79:1
With LON communica-
tion module: Control
unit is fault manager
(only for weather-com-
pensated control units)
79:0
Control unit is not fault
manager
7b:1
With LON communica-
tion module: The control
unit transmits the time
(only for weather-com-
pensated control units)
7b:0
Do not transmit time
7F:1
Detached house (only
for weather-compen-
sated control units)
7F:0
Apartment block
Separate adjustment of
holiday program and time
program for DHW heat-
ing, as option
80:1
A fault message is dis-
played, providing a fault
is active for at least 5 s
80:0
Immediate fault message
80:2
to
80:199
The fault message is is-
sued after a delay that is
adjustable from 10 s to
995 s; 1 step = 5 s
81:1
Automatic summer/win-
ter time changeover
81:0
Manual summer/winter
time changeover
81:2
Radio clock module is
automatically detected
81:3
With LON communication
module: The control unit
receives the time
82:0
Operation with natural
gas
82:
–
Never adjust
Code 2
(cont.)