Coding in the delivered condition
Possible change
Subscriber no.
77:1
LON subscriber number 77:2
to
77:99
LON subscriber number,
adjustable from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - ... = Vitotronic 200-H
99 = Vitocom
Note
Allocate each number
only
once.
DHW priority A1
A2:2
Cylinder priority to heat-
ing circuit pump
A2:0
Without cylinder priority
for heating circuit pump
DHW priority M2
A2:2
Cylinder priority applic-
able to heating circuit
pump and mixer
A2:0
Without cylinder priority
applicable to heating cir-
cuit pump and mixer
A2:1
Cylinder priority only ap-
plicable to mixer
A2:3
to
A2:15
Reduced priority applied
to mixer (the heating cir-
cuit receives a reduced
amount of energy)
Summer econ. A1/M2
A5:5
With heating circuit
pump logic function
(only for weather-com-
pensated control units)
A5:0
Without heating circuit
pump logic function
Min. flow temp. A1/M2
C5:20
Electronic minimum
flow temperature limit
20 °C (only for weather-
compensated control
units)
C5:1
to
C5:127
Minimum limit adjustable
from 10 to 127 °C (limited
by the boiler coding card)
Max. flow temp. A1/M2
C6:74
Electronic maximum
flow temperature limit
74 °C (only for weather-
compensated control
units)
C6:10
to
C6:127
Maximum limit adjustable
from 10 to 127 °C (limited
by the boiler coding card)
Code 1
(cont.)
38
Coding
5692
761
GB
Содержание Vitodens 200-W WB2B Series
Страница 105: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 105 Designs 5692 761 GB...
Страница 109: ...Parts lists cont 109 Parts lists 5692 761 GB...
Страница 110: ...Parts lists cont 110 Parts lists 5692 761 GB...
Страница 111: ...Parts lists cont 111 Parts lists 5692 761 GB...
Страница 118: ...118 5692 761 GB...
Страница 119: ...119 5692 761 GB...