Coding in the delivered condition
Possible change
DHW
56:0
Set DHW temperature
adjustable from 10 to
60 °C
56:1
Set DHW temperature
adjustable from 10 to
above 60 °C
Note
Maximum value subject
to boiler coding card.
Observe the max. per-
missible DHW tempera-
ture.
58:0
Without auxiliary func-
tion for DHW heating
58:10
to
58:60
Input of a second set
DHW value, adjustable
from 10 to 60 °C (observe
coding addresses "56"
and "63")
59:0
Cylinder heating:
Starting point -2.5 K
Stopping point +2.5 K
59:1
to
59:10
Starting point adjustable
from 1 to 10 K below the
set value
5b:0
DHW cylinder directly
connected to the boiler
5b:1
DHW cylinder connected
downstream of the low
loss header
60:20
During DHW heating,
the boiler water tem-
perature is max. 20 K
higher than the set
DHW temperature
60:5
to
60:25
The difference between
the boiler water tempera-
ture and the set DHW
temperature is adjustable
from 5 to 25 K
62:2
Circulation pump with
2 min run-on time after
cylinder heating
62:0
Circulation pump without
run-on
62:1
to
62:15
Run-on time adjustable
from 1 to 15 min
63:0
Without auxiliary func-
tion for DHW heating
(only for constant tem-
perature control units)
63:1
Auxiliary function: 1 x
daily
63:2
to
63:14
Every 2 days to every 14
days
63:15
2 x daily
Code 2
(cont.)
46
Coding
5692
761
GB
Содержание Vitodens 200-W WB2B Series
Страница 105: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 105 Designs 5692 761 GB...
Страница 109: ...Parts lists cont 109 Parts lists 5692 761 GB...
Страница 110: ...Parts lists cont 110 Parts lists 5692 761 GB...
Страница 111: ...Parts lists cont 111 Parts lists 5692 761 GB...
Страница 118: ...118 5692 761 GB...
Страница 119: ...119 5692 761 GB...