Installation at the installation site
VITOBLOC 200 EM-530/660
version
SCR
Installation instructions
29
5
8
41436
GB
6.8
Electrical connection
1
Cable entries
2
On-site terminal strips
3
TeleControl LAN
Fig. 16
Cable routing in the control panel
DANGER
Live components!
Death by electrocution on contact
Work on the machine may only be
carried out by qualified electricians.
The safety instructions must be
observed.
Isolate the machine from the power
supply before commencing electrical
work.
6.8.1 Power supply
(1) Open the control panel door.
(2) Remove the cover panel from the top of the
control panel and attach the on-site cable
entry for the mains power cable.
(3) Connect the mains power cable and
(if necessary) a PE-N jumper in the
control panel as per the wiring diagram.
(4) Route the power cable outside the cable trays
in cable conduits if necessary. Provide strain
relief fittings.
•
Do not route cables over objects with sharp
edges!
•
Do not route cables with sharp bends! Observe
bending radii!
•
Do not pull on the cables.
•
Route cables in such a way that there is no risk
of tripping!
•
Route cables in such a way that they cannot be
damaged!
(5) Do not fasten cables or the cable tray to the
CHP unit (vibration/sound transmission).
(6) Observe uninstalled minimum clearances!
(See section 5.3.2)