Transport, storage and siting
VITOBLOC 200 EM-530/660
version
SCR
Installation instructions
17
5
8
41436
GB
5.2
Storage
PLEASE NOTE
Incorrect storage!
Material damage due to corrosion
Protect the machine and its parts from
rust.
Prevent the formation of condensation.
DANGER
Incorrect storage!
Risk of explosion
Never store any flammable materials in
the vicinity of the CHP unit.
Protect the Vitobloc 200 EM-530/660 CHP unit
(versions SCR and SCR-ready) from moisture during
storage and transportation.
Max. relative humidity:
70 %
The machine must not be exposed to dust, sulphur or
air contaminated with halogens.
Perform a warranty preservation no later than
24 weeks after delivery.
5.3
Siting
The Vitobloc 200 EM-530/660 CHP unit (versions
SCR and SCR-ready) is sited in a locked plant room.
5.3.1 Conditions for siting
Before siting the CHP unit, take into consideration the
following points:
●
For servicing and maintenance purposes, maintain
a clearance as shown in the installation diagram
(Fig. 5).
●
The installation surface must be level (inclination
0° ± 1°) and have a sufficient load bearing
capacity.
●
The plant room must be equipped with a water
supply and a floor drain.
●
The humidity in the plant room must not exceed
70 %.
●
Any additional acoustic measures required must
be implemented by a suitable specialist contractor.
●
Restrict externally acting vibrations, e.g. via the
building structure or electromagnetic interference,
to an absolute minimum and document all such
influences during commissioning.
●
The installation room must be configured in
accordance with the applicable combustion
ordinance and applicable building
ordinances/regulations. For safe operation, it is
recommended that the CHP unit be integrated into
the relevant fire protection concept.
●
Provide a fire extinguisher in the plant room.
●
To increase safety for the operating personnel, we
recommend installing a CO detector in the
installation room.
DANGER
Differing ambient conditions!
Material damage due to malfunctions
Do not install in the same room as a
boiler system with atmospheric burner
or an NH
3
refrigeration unit with an
interconnected air supply.