Item
Description
Value
LE2 Default
For UL compliance, this field must not
exceed 50 seconds.
Release Duration
The length of time the extinguishants
are released.
60 – 500 seconds
120 seconds
Disablements Tab
Item
Description
Value
LE2 Default
Release Timer
This disables the
setting.
Enabled or Disabled
Enabled
Ground Trouble
This disables ground trouble monitoring.
For UL compliance, this field must be set to Enabled.
Enabled or Disabled
Enabled
Trouble Output
The trouble relay on each module can be disabled.
For UL compliance, this field must be set to Enabled.
Enabled or Disabled
Enabled
VES Fire Detection Systems
XT+ Releasing Control Unit Installation Manual
Version 1.00 | December 2018 | MAN-1252VES
Page 38
System Startup