WARNING!
Remove jumper J1 before operating the XT+ Releasing Control Unit at 230 VAC. Failure to remove
jumper J1 prior to operating at 240 VAC will cause permanent damage to the 5.25 Amp power supply.
Voltage
Jumper Required
120
Yes
240
No
Refer to "Installation" on page 17 for specific details about wiring the power supplies. Provide an AC power
connection to the terminal block from a 15 Amp branch circuit.
1. Connect a wire from the ground terminal (
) to the grounding block of the cabinet box.
2. Connect a wire from the grounding block of the cabinet box to a ground. Provide this connection in close
proximity to the cabinet box.
3. Connect a wire from the neutral terminal (N) to the neutral of the power source.
4. Connect a wire from the line terminal (L) to the line of the power source.
DIP Switches
DIP switches are located on the edge of the power supply.
5.25 Amp Power Supply
The following figure illustrates the location of DIP switches on the 5.25 Amp Power Supply:
Installation
VES Fire Detection Systems
XT+ Releasing Control Unit Installation Manual
Version 1.00 | December 2018 | MAN-1252VES
Page 21