Press
Enter
to turn on the extract output. The buzzer will sound on the Elite RS FACP.
The display will show:
Press
Enter
to re-enable the output and restore the Disablement condition.
Press
Enter
to select the Reserve output. When the Reserve output is selected, the
Reserve Cylinders LED will be illuminated and the LCD will display the following:
Press
Enter
to select the Main output.
Access Level 3
To enter Access Level 3, turn the Enable Access keyswitch and turn the Write Enable switch to the on (left)
position. The # on the LCD represents the number of updates to the XT module's configuration.
This is the number of times the extinguishant outputs have been calibrated. It is incremented each time the
following procedure is performed and cannot be reset. This functionality can be used to provide evidence of
tampering.
Set the Extinguishant Output Calibration
The extinguishing outputs (Exting.1 (Main) and Exting. 2 (Reserve)) are supervised for shorts and opens. Each
output is calibrated to the electrical characteristics of the specific devices that are connected to it. When a new
device is initially installed on this output, a trouble will likely occur and a recalibration will be required.
Press
Enter
, then
(+)
until the LCD displays:
Access Levels
VES Fire Detection Systems
XT+ Releasing Control Unit Installation Manual
Version 1.00 | December 2018 | MAN-1252VES
Page 33