NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
UL Compliance Limitations
In order for the product to comply with the requirements in the
Standard for Control Units and Accessories
for Fire Alarm Systems, UL 864 10th Edition
, certain programming features or options must be limited to
specific values or not used at all as indicated below.
Field
Configurable Range
UL Permitted Value / Range
Release Delay
0 - 60s
0 - 50s
Ground Trouble
Enabled
Disabled
Enabled
Trouble Output
Enabled
Disabled
Enabled
Release Pressure Switch Mode
Normal
Invert
Normal
Low Pressure Switch Mode
Normal
Invert
Normal
Abort Mode
Abort
Hold
Abort
Access Level 2 > Disable Exting. Release?
Disable
Enable
Enable
Power Supply DIP Switches
SW2
SW1
OFF / ON
OFF / ON
OFF
OFF