inputs of 120 VAC or 240 VAC. For more information about the power supplies and their functions, see
The power supply contains a jumper setting for changing from 120 VAC to 240 VAC. Check the jumper setting
prior to wiring and operating the 5.25 Amp Power Supply.
WARNING!
Remove jumper J1 before operating the unit at 240 VAC. Failure to remove jumper J1 prior to
operation will cause permanent damage to the power supply.
Confirm that the 5.25 Amp Power Supply is set for 240 VAC before operating. Permanent damage of the
power supply will result if the 120 VAC jumper setting exists while operating the power supply at 240 VAC.
High voltage is present on jumper pins. Remove AC power before changing jumper setting.
VES Fire Detection Systems
XT+ Releasing Control Unit Installation Manual
Version 1.00 | December 2018 | MAN-1252VES
Page 20
Installation