Item
Description
Value
LE2 Default
For UL compliance, this field must be set to
Normal.
Language
Some modules are factory fitted with an alternate
language to English. The alternate language can
be used by selecting Other.
English
Other
English
Output Mode
When set to Common, the two extinguishing out-
puts are released at the same time. When set to
Main / Reserve, output 1 will release and a Main /
Reserve selection option appears at Access
Level 2. The Reserve Cylinders LED will be illu-
minated and output 2 will release during the next
activation.
Common
Main / Reserve
Common
Activation Mode
By default, two devices (Coincidence) must be
active for a module to enter the Activated
condition. This setting can be used to allow any
Single active device to cause the module to enter
the Activated condition.
IMPORTANT!
Initiating devices must
be connected directly to the same panel
as the XT+ Releasing Control Unit.
(Devices in the same zone connected to
other network panels will not initiate a
release.)
Coincidence
Single
Coincidence
User Output Mode
This changes the function of the of the Supv ter-
minal.
Supervisory
Abort
Supervisory
Abort Mode
Abort switches are not permitted on systems inten-
ded to perform pre-action or deluge water func-
tions.
For UL compliance, this field must be set to Abort.
Abort
Hold
Abort
When the Manual Release input is configured for no delay, it will override an active Abort input. When the
Manual Release input is configured for pre-release delay, it will override an active Abort input and cause the
countdown to resume.