Item
Description
Value
LE2 Default
Name
This is the name used by LE2 to refer to the
XT+ Module.
XT+ Module
XT+ Module
First Activation Zone
The lowest numbered zone in the releasing area for
this module.
1-500
1
Last Activation Zone
The highest numbered zone in the releasing area
for this module.
1-500
2
Address
The address of the module.
1-15
1
The releasing area of a module must consist of one or more sequentially numbered zones. This range of zones is
defined by the first and last activation zones.
Initiating devices which are in this range of zones and are connected directly to the same panel as the XT+ will be
the only devices that will initiate a release. When configured for coincidence, any two of these devices will initiate
a release.
Devices outside this range or connected to other network panels will not initiate a release.
Times Tab
Item
Description
Value
LE2 Default
Reset Lock-Out Time
The length of time before the extin-
guishant outputs can be reset.
0 - 30 minutes
0 minutes
Release Delay
The delay between the activation of a
module and extinguishant release.
0 - 60 seconds
30 seconds
System Startup
VES Fire Detection Systems
XT+ Releasing Control Unit Installation Manual
Version 1.00 | December 2018 | MAN-1252VES