Fig. 1 

WAREMA BACnet 4M230.8I AP 

The WAREMA BACnet 4M230.8I AP sun shading actuator 

with 8 digital inputs and 4 relay outputs is a device for the 

operation of four sun shading drives

 

230 V AC (the fol-

lowing uses the sun shading actuator for four motors with 

eight push button inputs as an example).

A BACnet client can be used to switch and query the 

inputs and outputs via standard objects. The digital inputs 

are suitable for floating external push buttons. Under the 

cover, the device has a manual control level for the outputs 

(see  

Fig. 5) and two encoding switches for setting the actuator 

address and the baud rate.

The drives and the motor control unit are supplied via a 

230 V AC control line.

Intended use

The BACnet 4M230.8I AP is an electronic device for con-

trolling sun shading devices. The approval of the manufac-

turer must be obtained for any use of the device other than 

its intended purpose specified in these instructions.

Safety instructions

ARNING

W

 

The electrical installation (assembly)/dis-

mantling must be performed by a certified 

electrician in accordance with VDE 0100 

and/or with the standards and legal require-

ments pertaining to the respective country. 

The electrician must observe the installa-

tion notes and instructions included with 

the electrical devices supplied.

ARNING

W

 

If it a hazard-free operation cannot be 

assumed, the device must not be started 

or must be deactivated. This assumption is 

justified if:

    

  the housing or the connecting lines show 

signs of damage, 

    

  the device is no longer working.

ARNING

W

 

It is important to comply with the following 

points in the interest of personal safety.

 

 

Children may not play with the operating elements of 

the control unit or the remote control. Store remote 

controls out of reach of children.

 

 

Make sure that no persons or objects are in the path of 

the driven parts (internal and external venetian blinds, 

etc.).

 

 

Disconnect the device from the operating voltage if 

cleaning or other maintenance work must be per-

formed!

Function

A functional description of the  

WAREMA BACnet 4M230.8I AP can be found in the 

manual (art. no. 2051515).  

PICS (Protocol Implementation Conformance Statement) 

and BIBBs (BACnet Interoperability Building Blocks) can be 

found in the software manual (art. no. 2053952).
Documents pertaining to the sun shading actuator can be 

downloaded from 

www.warema.de/bacnet

 

Installation

Insert a slotted screwdriver (recommendation: 3.0 - 4.0 mm 

blade) into the respective cover opening (Fig. 4) and care-

fully pry open the hinged cover. Repeat the procedure for 

the second opening of the cover. After both latches have 

been unlatched,

the cover can be removed. 

Electrical connection

An on-site overload current protection device (fuse) and a 

disconnecting and isolating switch to switch off the entire 

unit must be provided.
The unit is electrically connected according to the wiring 

diagram on the other side of the page (Fig. 5).

Installation instructions

WAREMA BACnet 

4M230.8I AP

Valid from  

1st July 2022

Keep for future use.

Содержание BACnet 4M230.8I AP

Страница 1: ...annot be assumed the device must not be started or must be deactivated This assumption is justified if the housing or the connecting lines show signs of damage the device is no longer working ARNING W It is important to comply with the following points in the interest of personal safety Children may not play with the operating elements of the control unit or the remote control Store remote control...

Страница 2: ...ed LED Communication error CRC ERROR Red LED Communication error Framing ER ROR Red LED Incomplete frames Red LED Input bridged Yellow LED Output active Yellow LED Maintenance There are no parts inside the device that require mainte nance In the event of a malfunction the built in miniature fuses should only be replaced by a certified electrician Liability Failure to comply with the product inform...

Страница 3: ...age temperature 0 70 C Humidity not condensing 10 40 85 Frel Degree of soiling 2 Connection Connecting line Spring terminal U Contact Permissible line cross section max 2 5 mm Stripping length min 8 mm Motor outputs Spring terminals Permissible line cross section max 2 5 mm Stripping length min 8 mm Inputs Spring terminals Permissible line cross section max 2 5 mm Stripping length min 8 mm BACnet ...

Страница 4: ...B YCYM 2 2 0 8 mm Bus Bus 0 V Bus A Bus B 0 V to next bus device 2 PE N L connecting line 230 V AC 50 60 Hz 16 A 3 x 1 5 mm All bus lines from previous bus device Attention Only one motor can be connected per motor terminal set If interconnected the motor will be damaged The total power of all 4 outputs per fuse must not exceed 1000 VA All motor lines H05 RR F 4 G 0 75 BK type WAREMA All push butt...

Отзывы: