Technical data
BACnet 4M230.8I AP
min.
typ.
max.
Unit
Operating voltage
198
230
253
V AC
Mains frequency
50
50
60
Hz
Power consumption in standby
mode at 230 V AC
0.7
-
2.3
W
Output per drive*
Switching capacity 230 V AC/
cos φ = 0.6
500
VA
*The total power per fuse must not exceed 1000 VA.
BACnet interface
Protocol
BACnet MS/TP
Address range for BACnet
0 - 255 (0x00 to 0xFF)
Bus interface
RS485 (two-wire bus) with
potential equalisation in bus/
line topology, terminate with
120 Ω (
see Fig. 5, terminal
X11
) and activate BIAS resis-
tors in the router.
Transmission format
8 N 1
BACnet device profile
BACnet Application Specific Controller (B-ASC)
BACnet MS/TP in accordance with ISO 16484-5:2017
BACnet Protocol Revision 16
Inputs, local operating elements
Current, active
0.5
1
1.5
mA
Ambient conditions
Operating temperature
0
50
°C
Storage temperature
0
70
°C
Humidity
(not condensing)
10
40
85
%F
rel
Degree of soiling
2
Connection
Connecting line
Spring terminal U/Contact
Permissible line cross-section
max. 2.5 mm²
Stripping length
min. 8 mm
Motor outputs
Spring terminals
Permissible line cross-section
max. 2.5 mm²
Stripping length
min. 8 mm
Inputs
Spring terminals
Permissible line cross-section
max. 2.5 mm²
Stripping length
min. 8 mm
BACnet interface
Spring terminals
Permissible line cross-section
0.6 - 0.8 mm
∅
Stripping length
5 - 6 mm
Housing
Dimensions
See Fig. 4
Surface-mounted housing
degree of protection
IP30
Safety class
(PE is looped through)
I
Miscellaneous
Conformity
Specified under
This device complies with the EMC directives for use in
residential and commercial areas.
Article numbers
BACnet 4M230.8I AP
2047065
Strain relief set
for surface-mounted hous-
ing
1002236
WAREMA Renkhoff SE
Hans-Wilhelm-Renkhoff-Strasse 2
97828 Marktheidenfeld
Germany
Fuse protection
BACnet 4M230.8I AP
Quan-
tity
Fuse protection
BACnet 4M230.8I AP
1 x
6.3 AT H
3 ‒ 4 mm
158 mm
119 mm
132 mm
180 mm
60 mm
Fig. 4
Surface-mounted housing dimensions