The tables below describe DIP switch settings 1 through 4 of the 5.25 Amp Power Supply. For UL compliance,
DIP switches should be set to the defaults, as shown.
SW1&2 together define the Battery Load Test (also known as Battery Impedance Test)
Switch 1
Switch 2
Description
Off (DEFAULT)
Off (DEFAULT)
Recommended for standard operation. Load test
the battery every 59 minutes. Measured voltage
drop > 900mV fails the test.
Off
On
NOT USED. Load test the battery every 59
minutes. Measured voltage drop > 1100mV fails
the test.
On
Off
Disable trouble reporting of disconnected
standby batteries. Load test the battery every
minute. Measured voltage drop > 900mV fails the
test. This setting also masks BATTERY_MISSING
troubles.
On
On
Disable trouble reporting of standby battery
impedance. No load test performed.
Switch setting 3 is not used on the 5.25 Amp Power Supply and should be set to OFF.
SW4 defines Battery Manufacturer.
Switch 4
Description
On (DEFAULT)
Sets standby batteries for the Powersonic manufacturer.
Off
Sets standby batteries for the Yuasa manufacturer.
Other manufacturer batteries can be used. Consult the manufacturer's datasheet for proper settings.
Status Indicators
LED Indicator
Condition
AC NORMAL
The AC power is connected.
EARTH FLT
The 24V DC supply is connected to the ground.
CHARGER FAULT w/ abnormal
HEARTBEAT
An internal fault has been detected in the power supply module. The HEARTBEAT
indicator blinks different patterns to indicate the fault.
1-1 AC Power is on and 24V output is not in regulation.
1-2 The battery voltage is too high.
VES Fire Detection Systems
XT+ Releasing Control Unit Installation Manual
Version 1.00 | December 2018 | MAN-1252VES
Page 22
Installation