The Vertiv VRC-S, painted RAL 7021 as are its main components, may be controlled through the Geist rPDU, which is
network-enabled and permits remote monitoring and management over a network. A display that may be installed on the
rack's back door, provides local monitoring and control of the Vertiv™ VRC.
The Vertiv™ VRC-S easily accepts either the Vertiv™ Liebert® PSI5 or Vertiv™ Liebert® GXT5 UPS and the Geist rPDU
family of products to provide conditioned and backup power to the rack equipment.
IMPORTANT! If a UPS is installed, it should be installed immediately above the Vertiv VRC. Installing
the UPS higher in the rack could result in a tipping hazard.
2.3 Vertiv VRC Characteristics
The Vertiv VRC cooling unit may be either 120 V, 208 V or 230 V. Each unit will deliver up to 3.5 kW of cooling/heat removal
to the rack-mounted equipment.
The Vertiv™ VRC-S must be installed indoors in an environment with a temperature range of 18°C-30°C (64.4°F-86°F) and
less than 80% relative humidity (non-condensing).
For VRC-S with VRC split the outdoor temperature range is -15°C (5°F) to 45°C (113°F).
For VRC-S with VRC split lee temp the outdoor temperature range is -34°C (-29.2°F) to 45°C (113°F).
2 Introduction
8
Vertiv™ VRC-S User Manual
Содержание VRC-S
Страница 1: ...VRC S User Manual...
Страница 10: ...1 Important Safety Instructions 6 This page intentionally left blank Vertiv VRC S User Manual...
Страница 20: ...2 Introduction 16 This page intentionally left blank Vertiv VRC S User Manual...
Страница 38: ...5 Operation 34 This page intentionally left blank Vertiv VRC S User Manual...
Страница 64: ...9 Appendices 60 This page intentionally left blank Vertiv VRC S User Manual...
Страница 65: ...Vertiv VRC S User Manual...