background image

Split System Condensing

Unit:

VRC352KIT

Input power

hardwired L+N+PE

Voltage, Frequency

230 Vac, 50/60 Hz

Full Load Amperage (FLA)

6,5 A

Refrigerant type (pre-
charged)

R410A, outdoor unit 900 g (1.98 lb)

Dimensions H, W, D

527 mm, 282 mm, 1158 mm ( 20.75 in., 11.10 in., 45.60 in.)

Net weight

68 kg (150 lb.)

Shipping dimensions H,W,D

755 mm, 480 mm, 1350 mm (29.72 in., 18.90 in., 53.20 in.)

Shipping weight

85 kg (187 lb.)

IP Code

IPX4 (IEC 60529)

Outdoor temperature range

-34°C (-29.2°F) to 45°C (113°F)

Noise level

<55 dB(A)

Certifications

CE Marked, Complies with EN 60335-1; EN 60335-2-40, EN 55014-1, EN 55014-2, EN 61000-3-2, EN 61000-3-3, RoHS
Compliant (EN 50581)

Split System Condensing

Unit:

VRC302KIT

Input power

Hardwired L+N+PE

Voltage, Frequency

230 Vac, 50/60 Hz

Full Load Amperage (FLA)

6,5 A

Refrigerant type (pre-
charged)

R410A, outdoor unit 900 g (1.98 lb)

Dimensions H, W, D

527 mm, 282 mm, 786 mm ( 20.75 in., 11.10 in., 30.94 in.)

Net weight

44 kg (97 lb.)

Shipping dimensions H,W,D

750 mm, 480 mm, 970 mm (29.53 in., 18.90 in., 38.19 in.)

Shipping weight

70 kg (154 lb.)

IP Code

IPX4 (IEC 60529)

Outdoor temperature range

-15°C (5°F) to 45°C (113°F)

Noise level

<55 dB(A)

Certifications

CE Marked, Complies with EN 60335-1; EN 60335-2-40, EN 55014-1, EN 55014-2, EN 61000-3-2, EN 61000-3-3, RoHS
Compliant (EN 50581)

8 Specifications

51

Vertiv™| VRC-S User Manual

Содержание VRC-S

Страница 1: ...VRC S User Manual...

Страница 2: ...mages resulting from use of this information or for any errors or omissions Refer to other local practices or building codes as applicable for the correct methods tools and materials to be used in per...

Страница 3: ...the Rack Cooling Unit Vertiv VRC S with VCR Split 24 4 5 Install the Vertiv Vertiv VRC S with Vertiv VRC Split 24 4 6 Connect Power to the Backup Fan 24 4 7 Connect Power to the Condensate Pump 25 4 8...

Страница 4: ...0 V NAM 44 8 4 Vertiv VRC S with VRC split lee temp 208V NAM 46 8 5 Vertiv VRC S with VRC self contained 230V EMEA 48 8 6 Vertiv VRC S with VRC split and VRC S with VRC split lee temp 230V EMEA 49 8 7...

Страница 5: ...r rack equipment should be installed in the positions just above the Vertiv VRC then installing lighter equipment in the upper positions WARNING Risk of shock loading Can cause equipment damage The Ve...

Страница 6: ...t suitable to fit below the skid and or unit to prevent exterior and or underside damage NOTICE Risk of improper storage Keep the unit upright indoors and protected from dampness freezing temperatures...

Страница 7: ...ure to do so may result in serious injury or death Rack PDU units contain no user serviceable parts other than the field replaceable plastic carrier not installed on all models that is designed to be...

Страница 8: ...d use the UPS in the following environments Temperature 32 F 122 F 0 C 50 C relative humidity 0 to 95 Out of direct sunlight Away from heat source Stable surface not subject to vibrations or shocks Aw...

Страница 9: ...watches rings and other metal objects Use tools with insulated handles Wear rubber gloves and boots Do not lay tools or metal parts on top of batteries Disconnect charging source prior to connecting o...

Страница 10: ...1 Important Safety Instructions 6 This page intentionally left blank Vertiv VRC S User Manual...

Страница 11: ...and less than 80 relative humidity non condensing Operating the Vertiv VRC S in extreme environments may cause condensation inside the cabinet The VRC S is not environmental neutral The user is encour...

Страница 12: ...UPS is installed it should be installed immediately above the Vertiv VRC Installing the UPS higher in the rack could result in a tipping hazard 2 3 Vertiv VRC Characteristics The Vertiv VRC cooling un...

Страница 13: ...em UPS that continuously conditions and regulates its output voltage The Liebert GXT5 supplies microcomputers and other sensitive equipment with clean sine wave input power Upon generation AC power is...

Страница 14: ...2 5 Vertiv VRC S System Connections Figure 2 2 One Line Diagram of Vertiv VRC S self contained Connection NAM without Liebert GXT5 2 Introduction 10 Vertiv VRC S User Manual...

Страница 15: ...Figure 2 3 One Line Diagram of Vertiv VRC S self contained Connection EMEA without Liebert GXT5 2 Introduction 11 Vertiv VRC S User Manual...

Страница 16: ...Figure 2 4 One Line Diagram of Vertiv VRC S self contained Connection EMEA with Liebert GXT5 2 Introduction 12 Vertiv VRC S User Manual...

Страница 17: ...Figure 2 5 One Line Diagram of Vertiv VRC S split Connection EMEA without Liebert GXT5 2 Introduction 13 Vertiv VRC S User Manual...

Страница 18: ...Figure 2 6 One Line Diagram of Vertiv VRC S Split Connection EMEA with Liebert GXT5 2 Introduction 14 Vertiv VRC S User Manual...

Страница 19: ...Figure 2 7 One Line Diagram of Vertiv VRC S Split Connection NAM without Liebert GXT5 2 Introduction 15 Vertiv VRC S User Manual...

Страница 20: ...2 Introduction 16 This page intentionally left blank Vertiv VRC S User Manual...

Страница 21: ...impact damage Store the unit in the original packaging indoors in an area protected from excessive dirt debris and contact damage until final installation Observe the following requirements and the c...

Страница 22: ...ls shipped with the Vertiv VRC S They can be found attached to the interior of the Vertiv VR rack Cut the plastic wrapping from the rack using a knife along the corrugated padding to prevent damaging...

Страница 23: ...rtiv VR a 19 in EIA server rack will have these components factory installed Thermal separation Rack closing kit Sensors for temperature and door contact Backup fan Geist rPDU factory programmed Liebe...

Страница 24: ...splay and Display Magnetic Box 10 m Cable of Display L shape Mounting Rail Kit Cage Nuts M6 Pan Head Screws M6x12 Torx T30 Center Screws M5x12 Torx T20 USB Converter Cable Side Panel Front Panel Manua...

Страница 25: ...v VRC manual before Section 4 1 Install the filter in the Vertiv VRC The cooling unit has a filter on the top rear that collects particulates from the return air going back into the Vertiv VRC The bra...

Страница 26: ...to help cooling air circulate efficiently inside the rack equipment section of Vertiv VRC S Cage nuts should have been attached to the rails before the Vertiv VRC was inserted into the cabinet Air ba...

Страница 27: ...Figure 4 1 Air Barriers 800 mm 31 5 in Figure 4 2 Attach Air Baffles 800 mm 31 5 in Rack 4 Installation 23 Vertiv VRC S User Manual...

Страница 28: ...manual NOTE Piping between the indoor and outdoor units must be routed so that it does not block the IT space above and does not extend into the space between the EIA rails 4 6 Connect Power to the Ba...

Страница 29: ...on the factory installed Geist rPDU for proper operation The Geist rPDU is marked to facilitate proper connection To connect power to the condensate pump 1 Connect the power cord to the condensate pum...

Страница 30: ...r the door or laid on the Vertiv VRC If the display is to be placed on the cooling unit simply attach the 20in 50cm communication cable to the rack and to the rear of the cooling unit as shown Figure...

Страница 31: ...ables for the local display and the fan 1 Open the rear door of the Vertiv VRC S 2 Route the local display and fan cables around the outside edge of the fan housing and up to the top of the door 3 Use...

Страница 32: ...bled permitting monitoring and managing the Vertiv VRC over a network Use the supplied cable to set up the connection the cable has an RJ 45 connector on one end and a USB connector on the other To co...

Страница 33: ...ent air The Vertiv VRC S includes a flexible duct and two ceiling tiles one to move warm air from the Vertiv VRC C into the ceiling or and adjacent area through the duct The second tile is for make up...

Страница 34: ...remove packaging from or prepare the unit for installation Vertiv recommends installing equipment in the Vertiv VR from bottom to top to promote a lower center of gravity All equipment must be install...

Страница 35: ...ertiv Intelligence Director which is embedded in the Geist rPDU 5 3 1 Changing Settings with the Geist rPDU Using the Geist rPDU to monitor and manage the Vertiv VRC S requires connecting the rPDU to...

Страница 36: ...ngs Item Description 1 Component Status Column 2 Change Configuration Settings Icon 3 Component Name 4 Current Readings 5 Additional Information Table 5 1 Geist rPDU Sensor Page Vertiv VRC Settings De...

Страница 37: ...DU and Liebert GXT5 In case of versions with integrated Liebert GXT5 the aggregation function in the GeistrPDU web UI needs to be enabled Geist rPDU Manual for more information Figure 5 2 Aggregation...

Страница 38: ...5 Operation 34 This page intentionally left blank Vertiv VRC S User Manual...

Страница 39: ...the maximum rated value The Vertiv VRC s maximum load at 30 C 86 F is 3 3 kW the Vertiv VRC s cooling module is rated to remove 3 5 kW worth of heat Fan malfunction Contact Vertiv Technical Support Co...

Страница 40: ...representative about obtaining a Vertiv Geist SwitchAir Heat sensor is incorrectly programmed Reprogram the high temperature setpoint via the rack PDU network card or contact Vertiv Technical Support...

Страница 41: ...hen a UPS general alarm appears Table 6 3 Audible alarm Descriptions NOTE When an alarm is indicated an alarm message is logged See Liebert GTX5 User Manual that describes the alarm messages When a fa...

Страница 42: ...the LCD select Main Menu About PROBLEM CAUSE SOLUTION UPS fails to start UPS is short circuited or overloaded Ensure UPS is Off Disconnect all loads and ensure nothing is lodged in output receptacles...

Страница 43: ...updated in slave boards updt IMD 02 IMD 03 IMD 3 Firmware update in progress rset dflt IMD 02 IMD 03 IMD 3 Following user action rset Reset will appear during a parameter reset sequence During a param...

Страница 44: ...tion Contact Vertiv Technical Support LowPressure Insufficient air flow Remove obstruction or debris from air inlets Fan malfunction Contact Vertiv Technical Support EEV malfunction Contact Vertiv Tec...

Страница 45: ...6 mm 1385 mm 84 in 24 6 in 54 5 in 2396 mm 626 mm 1385 mm 94 3 in 24 6 in 54 5 in 2396 mm 826 mm 1385 mm 94 3 in 32 5 in 54 5 in rPDU Pre installed in rack NU30021 rPDUsub type Switched rPDUtype Outle...

Страница 46: ...t 419 kg 924 lb 361 kg 796 lb 397 kg 876 lb 437 kg 964 lb Sound At 60 fan speed and 40 compressor speed 52 5 dBA 1 m 52 5 dBA 1 m 52 5 dBA 1 m 52 5 dBA 1 m Rack dimensions U H W D 42U 2000 mm 800 mm 1...

Страница 47: ...2 SMTP SMTPS DHCP SNMP v1 v2c v3 LDAP NTP SSH and Syslog Certifications Agency approvals UL c UL Listed 60950 RoHS Compliant FCC Part 15 Class A Conformance UL c UL Listed 60950 RoHS Compliant FCC Pa...

Страница 48: ...mm 626 mm 1385 mm 84 in 24 6 in 54 5 in 2396 mm 626 mm 1385 mm 94 3 in 24 6 in 54 5 in 2396 mm 826 mm 1385 mm 94 3 in 32 5 in 54 5 in rPDU Pre installed in rack NU30021 rPDUsub type Switched rPDUtype...

Страница 49: ...densate pump tube length 7 5 m 24 ft NOTE Condenser will be shipped separate to customer Split System Condensing Unit VRC351KIT Input power hardwired L1 L2 L3 G Voltage Frequency 208 230 Vac 60 Hz Ful...

Страница 50: ...ched rPDUtype Outlet Level Monitoring Outlet Level Monitoring Voltage 208 V 208 V Input current 30 A 30 A Regularoty derated input current North America 24 A 24 A rPDUrated maximum 4 9 kW 4 9 kW Horiz...

Страница 51: ...PDU Condensate pump tube length 7 5 m 24 ft Certifications UL 1995 CSA 22 2 NO 236 11 NOTE Condenser will be shipped separate to customer Split System Condensing Unit VRC351KIT Input Power hardwired L...

Страница 52: ...mm 94 3 in 24 6 in 54 5 in 2396 mm 826 mm 1385 mm 94 3 in 32 5 in 54 5 in rPDU Pre installed in rack GU30017L Category Switched Sub Category Outlet Level Monitoring EC Voltage 200 240 V Current 32 A V...

Страница 53: ...Us VRCS3350 230VS VRCS3350 230VSL VRCS3300 230VS VRCS3300 230VSL VRCS3307 230VS VRCS3307 230VSL VRCS3357 230VS VRCS3357 230VSL Configured system weight 270 kg 595 lb 225 kg 496 lb 261 kg 575 lb 288 kg...

Страница 54: ...Syslog TACACS Certifications Agency approvals CEMarked Complies with EN 55032 and EN 55024 Complies with IEC 60950 1 CB Certificate Available RoHS Compliant RCM Mark EMC Only China RoHS C Mark Split S...

Страница 55: ...335 2 40 EN 55014 1 EN 55014 2 EN 61000 3 2 EN 61000 3 3 RoHS Compliant EN 50581 Split System Condensing Unit VRC302KIT Input power Hardwired L N PE Voltage Frequency 230 Vac 50 60 Hz Full Load Ampera...

Страница 56: ...94 3 32 5 54 5 Certifications CEMarked rPDU Pre installed in rack GU30017L Category Switched Sub Category Outlet Level Monitoring EC Voltage 200 240 VAC Current 32 A VA per Input 7 3 kW 230 V Frequenc...

Страница 57: ...EN 61000 3 2 EN 61000 3 3 RoHS Compliant UPS Pre installed in rack GXT5 6000IRT5UXLE Rating 6000 VA 6000 W system limited IT load max 3 5 kW Form factor 5U Unit dimensions HxDxW Inches 217 mm x 630 mm...

Страница 58: ...Temperature 15 C to 40 C 5 F to 104 F Relative Humidity 0 95 non condensing Operating Elevation Up to 3 000 m 9 842 5 ft at 25 C 77 F without derating Audible Noise 55 dBA at 1 meter from the front 5...

Страница 59: ...32 5 54 5 2134mm 626mm 1385mm 84 24 6 54 5 2396mm 626mm 1385mm 94 3 24 6 54 5 2396mm 826mm 1385mm 94 3 32 5 54 5 rPDU Pre installed in rack GU30017L rPDUsub type Switched rPDUtype Outlet Level Monito...

Страница 60: ...nit VRC302KIT Input Hardwired L N PE Voltage Frequency 230 Vac 50 60 Hz Full Load Amperage FLA 6 5 A Refrigerant type pre charged R410A outdoor unit 900 g 1 98 lb Dimensions H W D Inches 527 mm 282 mm...

Страница 61: ...16 9 Unit weight 70 8 kg 156 lb Input AC Parameters Operating Frequency Nom 50 or 60 Hz factory default is 50 Hz User configurable VAC 200 208 220 230 240 VAC Adjustable using operation display confi...

Страница 62: ...le Noise 55 dBA at 1 meter from the front 50 dBA at 1 meter from rear or sides Agency Safety IEC62040 1 2008 version GS mark EMI EMC C Tick EMC IEC EN AS 62040 2 2nd Ed Cat 2 Table 6 ESD IEC EN EN6100...

Страница 63: ...rflowis unobstructed External ventilation is adequate to supply makeup air for the Vertiv VRC System is not closed External air is within a temperature range of 64 4 F 86 F 18 C 30 C condensing and le...

Страница 64: ...9 Appendices 60 This page intentionally left blank Vertiv VRC S User Manual...

Страница 65: ...Vertiv VRC S User Manual...

Страница 66: ...e trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accuracy and completeness here Vertiv Group Corp assumes no responsibility...

Отзывы: